'Visual Inspection findings: A visual inspection of the tank and its affiliated <br /> pumps, piping and ancillary equipment did not reveal signs of leaks, corrosion, <br /> �Iveld cracks or breaks, or scrapes in protective coating which may cause a <br /> release from the tank system. A description of all discrepancies noted during the <br /> visual inspection is included with this report. Initials-. <br /> Seismic/Anchoring: <br /> Civil engineer wet stamped seismic/dynamic/hydrostatic load calculations <br /> provided as Attachment "A" <br /> Seismic/Anchoring findings: The tank as designed and operated, and the <br /> containment area in which it is located are adequately anchored and are <br /> eismically sound. Initials: <br /> Leak Test: 191(g)(9)/192(k)(1 0) <br /> The waste oil storage tank and ancill ry equipment were sealed <br /> and subjected to a slight positive pressure. A bubble test was <br /> performed on all tank seams and connections with no indication of <br /> leakage and good pressure retention. The secondary containment <br /> space was completely empty. <br /> Integrity testing findings: Based on the above noted integrity test and the results <br /> Ibtained from that test, the tank has sufficient integrity for its intended use. <br /> nitials: K�3 <br /> Tank Drawing: 191(g)(2)(E)/l 92(k)(2)(E)) <br /> Tank and fittings: See Attachment "E" <br /> Tank Dimensions (primary storage): <br /> 5-0" wide x 2'-8"deep <br /> Stockton Honda 5 Title 22 Waste Oil Assessment <br />