Laserfiche WebLink
Outlook <br /> Re: PR0231148-642 N Hunter St-CL21 <br /> From Saetern,Kristina Gaen[EHD] <ksaetern@sjgov.org> <br /> Date Thu 3/12/2026 12:35 PM <br /> To Star Gas<parkpetroleum@gmail.com> <br /> Hello, <br /> Thank you for submitting your RTC.Please see the following violations and the EHD response: <br /> Violation#10-2030074-Annual Monitoring System Certification Form to the CUPA within 30 days of completion of the test. <br /> • This violation will stand due to the facility was late by 61 days.Please provide a statement. <br /> Violation#11-2030048-Sec containment testing conducted per requirements&records kept for 36 mths <br /> • This violation will stand.During the time of inspection,no records of test were observed on site.Provide a statement and keep a copy of the <br /> 7/11/2023 secondary containment testing on site. <br /> Violation#13-2010017-Spill bucket testing results submitted to the UPA within 30 days of testing. <br /> • Provide a statement. <br /> Violation#30-2060015-Leak detection equipment located so leak is detected at the earliest possible <br /> opportunity <br /> • During the time of inspection,this violation was not corrected.Provide a statement of how this facility will ensure the monitoring equipment is <br /> maintained and located to detect a leak at the earliest opportunity. <br /> Violation#53-2010007-Submitted/maintained current Cert of Financial Responsibility/mech of financial assurance <br /> Vi-el-:44-e.19 459. -2030013 BE)imspeetiems eempleted at least every 3E)days amd meet all requirememts Glesed <br /> Violation#58-2010015-Copies of Facility Employee Training Certificates maintained. <br /> • Per the Corrective Action,please provide the records. <br />