CONTROL SCHEMATIC
<br />CONTROL FOR CONTROL FOR
<br />PUMP #1 PUMP #3
<br />C
<br />TRANSFORMER TRANSFORMER
<br />480/120 VOLTS 480/120 VOLTS
<br />HAND -OFF -AUTO SWITCH HAND -OFF -AUTO SWITCH
<br />STARTER OVER HAND OFF AUTO STARTER
<br />ND OFF -AUTO -O
<br />HA
<br />VER
<br />COIL COAD COILS LOAD
<br />ly
<br />PRESSURE \
<br />PRESSURE SWITCH
<br />SWITCH SPIN BUBBLER SPIN
<br />BUBBLER DOWN ETM MIDDLE DOWN ETM
<br />PUMP #1 TIME LEVEL TIME
<br />LOW LEVEL DELAY DELAY
<br />SPIN PIN
<br />OWN DOWN
<br />TIM TIME
<br />DELA DELAY\
<br />—0
<br />-E 130ol—LE Oa S�wt�1o� �ti'='coon
<br />PRESSURE PRESSURE -1* t
<br />SWITCH SWITCH our o1= 'PLG
<br />BUBBLER BUBBLER
<br />PUMP #2 ALARM
<br />ENGINE DRIVEN VERY
<br />HIGH LEVEL HIGH LEVEL 0
<br />ELECTRICAL CONTRACTORS
<br />WORK REQUIRED MATERIAL REQUIRED
<br />1. PROVIDE THE COMBINATION MOTOR STARTER AS DESCRIBED. 1. QUAN 1, COMBINATION MOTOR STARTER, TO INSTALL IN THE
<br />2. PROVIDE THE CONDUCTOR AND CONDUIT AS DESCRIBED. SPACE BELOW THE EXISTING MOTOR STARTER. THE STARTER
<br />3. REMOVE THE BUBBLER CONTROL FROM THE PANEL SHALL BE A DUPLICATE OF THE EXISTING MOTOR CONTROLS,
<br />INCLUDING DRAWOUT BUCKET, IF AVAILABLE; OR EQUIVALENT
<br />DOOR AND INSTALL ON THE DOOR OF THE PANEL BELOW SQUARE D, GE, OR CH WITH DRAWOUT BUCKET IF AVAILABLE,
<br />THE PG&E METER PANEL. NEMA SIZE #3, FVNR, WITH CIRCUIT PROTECTOR, HOA SWITCH,
<br />4. INSTALL ANOTHER PRESSURE SENSOR FOR PUMP #2. RED RUNNING LIGHT, GREEN OFF LIGHT, RUNNING TIME METER,
<br />6. INSTALL THIS MOTOR STARTER IN THE SPACE BELOW THE CONTROL TRANSFORMER, AND RESET BUTTON.
<br />EXISTING MOTOR STARTER. 2. #4 AWG, CU, THHN CONDUCTOR.
<br />5. INSTALL THE CONDUCTOR AND CONDUIT AS SHOWN BETWEEN 3• #6 AWG, CU, THHN CONDUCTOR.
<br />THE MOTOR STARTER AND THE MOTOR. RUN TO BE UNDER THE 4. #8 AWG, CU, THHN CONDUCTOR.
<br />5. 1" RIGID STEEL GALVANIZED AND NECESSARY
<br />FLOOR. SUPPORT AS REQUIRED BY THE CODE. FITTINGS.
<br />6. OTHER WORK AS NECESSARY TO PROVIDE A SYSTEM THAT 6. PRESSURE SENSING SWITCH FOR THIRD PUMP, SQUARE D
<br />OPERATES PROPERLY. CLASS 9012, TYPE AMWI, RANGE 0.25 TO 2.5 #
<br />7. CLEAN UP OF THE SITE TO RETURN IT AT LEAST TO THE DIFFERENTIAL 0.2 TO 2.0 #
<br />CONDITION PRIOR TO THE START OF THE WORK. 7. MISCELLANEOUS EQUIPMENT NECESSARY TO COMPLETE
<br />THE JOB, PROVIDE A WORKING SYSTEM, AND MEET ALL THE
<br />APPLICABLE CODE REQUIREMENTS.
<br />REFERENCES
<br />1. Tn1F a. ARTICLE 6, 1540. (a). I
<br />DrASION INDUSTRIAL SAFETY.
<br />CONSTRUCTION SAFETY ORDERS
<br />2. WILE 7110.
<br />CONTRACTORS LICENSE LAW
<br />—1-800-227-2600 —
<br />SPECIFICATIONS
<br />1. PART 3, TITLE 24, CALIFORNIA CODE OF REGULATIONS
<br />(CALIFORNIA ELECTRICAL CODE)
<br />2. UL OR APPROVED EQUAL TESTING ORGANIZATION.
<br />3. CITY OF STOCKTON AND COUNTY OF SAN JOAQUIN
<br />REGULATIONS.
<br />4. OSHA REGULATIONS.
<br />5. SEISMIC REQUIREMENTS FOR ZONE #3.
<br />GEIB ENGINEERING
<br />7315 WOODSIDE DRIVE
<br />STOCKTON, CA 95207
<br />PHONE 209-473-2230
<br />FAX 209-478-0272
<br />ORIGINAL SCALE IN INCHES
<br />FOR REDUCED PLAN
<br />0 1 2 3
<br />CHECKED BY: A� 7/'1f7
<br />DATE
<br />F., C/ Y/-//19-
<br />SENIOR ENGINEER: .�,►�7
<br />DATE
<br />APPROVAL RECOMMENDED-
<br />DATE
<br />ELECTRICAL SCHEMATIC
<br />PG&E
<br />INCOMING
<br />SERVICE
<br />MAIN CIRCUIT
<br />BREAKER
<br />200 AMP
<br />3 POLE
<br />480 VOLTS
<br />TRANSFORMER
<br />480/120 VOLT
<br />1 PHASE
<br />MODIFIED INCOMING
<br />SERVICE AND
<br />CONTROL PANEL
<br />TO LIGHTS,
<br />RECEPTACLES
<br />BATTERY CHARGER
<br />PURGE CONTROL
<br />SAMPLER
<br />MISCELLANEOUS
<br />C NEMA 1, SIZE #3
<br />COMBINATION FVNR
<br />PUMP#3 MOTOR STARTER
<br />COMBINATION WITH HOA, RTM, OFF
<br />STARTER AND RUN LIGHTS.
<br />RESET BUTTON,
<br />AND CONTROL
<br />TRANSFORMER
<br />3—#6 AWG CU THHN &
<br />1—#8 AWG CU THHN GND.
<br />IN 1 " RIGID STEEL
<br />GALVANIZED CONDUIT.
<br />PUMP #3
<br />30 HP
<br />MOTOR
<br />0
<br />1
<br />PUMP#1 C
<br />COMBINATION
<br />STARTER
<br />aaw I By
<br />PUMP #1
<br />30 HP
<br />MOTOR
<br />NEMA 1, SIZE #3
<br />COMBINATION FVNR
<br />MOTOR STARTER
<br />WITH HOA, RTM, OFF
<br />AND RUN LIGHTS.
<br />RESET BUTTON,
<br />AND CONTROL
<br />TRANSFORMER
<br />Coll
<br />RECORD D AWING
<br />Corrections By
<br />No Changes By
<br />Date �llll�
<br />Any Person Using This Drawing Should Vorlfy
<br />All Information By Inspecting The Site Of Work -
<br />K KJ ELDSEN
<br />S SINNOCK
<br />N NEUDECK
<br />INC. Consulting Engineers
<br />and Land Surveyors
<br />Post Office Box 844
<br />1113 W. Fremont Street
<br />Stockton, CA 95201-0844
<br />(209) 946-0268
<br />WEST LANE HEIGHTS
<br />PUMPING PLANT EXPANSION
<br />L
<br />ELECTRICAL REQUIREMENTS
<br />DEPARTMENT OF PUBLIC WORKS
<br />CITY OF STOCKTON, CALIFORNIA
<br />SCALE: NO SCALE APPROVED BY: DATE: SHEET NO.
<br />DESIGNED BY: CEG 1p 6
<br />DRAWN BY: CEG OF 6 SHTS
<br />CHECKED BY: KLK PROJECT NO.
<br />CITY ENGINEER
<br />RECORD DWG: STOCKTON, CALIF.
<br />3 9'? /. 5G
<br />0
<br />SWITCHBOARD
<br />300 AMP, 480 VOLT, 3 PHASE,
<br />4 WIRE
<br />LIGHTING
<br />PANEL
<br />4��D
<br />MAIN
<br />CIRCUIT
<br />CIRCUIT
<br />BREAKER
<br />BREAKER
<br />200 AMP
<br />LIGHTING PANEL
<br />F
<br />PG&E
<br />CIRCUIT
<br />PUMP #1
<br />PROTECTOR
<br />30 HP
<br />METERING
<br />FVNR
<br />O
<br />STARTER
<br />HOA
<br />WITH
<br />O
<br />DISCONNECT
<br />RESET RTM
<br />PANEL
<br />CIRCUIT
<br />PROTECTOR
<br />PUMP #3
<br />30 HP
<br />FVNR
<br />O
<br />STARTER
<br />HOA
<br />WITH
<br />O
<br />K
<br />DISCONNECT
<br />RESET RTM
<br />ON
<br />1,.jC>7_PULL
<br />SECTION
<br />PULL SECTION
<br />RECORD D AWING
<br />Corrections By
<br />No Changes By
<br />Date �llll�
<br />Any Person Using This Drawing Should Vorlfy
<br />All Information By Inspecting The Site Of Work -
<br />K KJ ELDSEN
<br />S SINNOCK
<br />N NEUDECK
<br />INC. Consulting Engineers
<br />and Land Surveyors
<br />Post Office Box 844
<br />1113 W. Fremont Street
<br />Stockton, CA 95201-0844
<br />(209) 946-0268
<br />WEST LANE HEIGHTS
<br />PUMPING PLANT EXPANSION
<br />L
<br />ELECTRICAL REQUIREMENTS
<br />DEPARTMENT OF PUBLIC WORKS
<br />CITY OF STOCKTON, CALIFORNIA
<br />SCALE: NO SCALE APPROVED BY: DATE: SHEET NO.
<br />DESIGNED BY: CEG 1p 6
<br />DRAWN BY: CEG OF 6 SHTS
<br />CHECKED BY: KLK PROJECT NO.
<br />CITY ENGINEER
<br />RECORD DWG: STOCKTON, CALIF.
<br />3 9'? /. 5G
<br />0
<br />
|