Laserfiche WebLink
I k. Violation of California Fire Code, Article 80, section 8003.3.1.4, failure to <br /> 2 provide emergency power in lieu of stand-by power for(1) exhaust ventilation, including the power <br /> 3 supply for treatment systems, (2) gas detection systems, (3) emergency alarm systems, and (4) <br /> 4 temperature-control systems; <br /> 5 1. Violation of California Fire Code, Article 80, section 8003.3.1.6, failure to <br /> 6 provide a continuous gas-detection system which will detect the presence of gas at or below the <br /> 7 permissible exposure limit and initiate a local alarm and transmit a signal to a constantly attended <br /> 8 control station; <br /> 9 In. Violation of California Fire Code, Article 80, section 8004.2.3.7.3, failure to <br /> 10 have internally sprinkerled exhausted enclosures; <br /> 11 n. Violation of California Fire Code, Appendix VI-G, Reference Table from the <br /> 12 Uniform Building Code- Required Separation in Buildings of Mixed Occupancy(Hours), failure to <br /> 13 maintain as separate the repair shop and chlorine storage and transferring process; there must be a 2- <br /> 14 hour occupancy separation between the chlorine transferring room (H-2 occupancy) and shop area <br /> 15 (B occupancy); <br /> 16 0. Violation of California Fire Code, Article 80, sections 8004.2.2, failure to <br /> 17 dispense and use hazardous materials in open containers or systems in accordance with the <br /> 18 California Fire Code. Additionally, pursuant to section 8001.4.2, containers, cylinders and tanks <br /> 19 shall be designed and constructed in accordance with nationally recognized standards. <br /> 20 P. Violation of California Fire Code, Article 80, section 8003.1.3.3, failure to <br /> 21 provide adequate secondary containment for hazardous materials liquids and solids; <br /> 22 q. Violation of California Fire Code, Article 80, section 8001.11.9, failure to <br /> 23 provide shelving of substantial construction, adequately braced and anchored; <br /> 24 r. Violation of California Fire Code, Article 80, section 8004.1.4, failure to <br /> 25 provide spill control and secondary containment for hazardous materials liquids; <br /> 26 S. Violation of California Fire Code, Article 80, section 8004.1.8, failure to post <br /> 27 signs prohibiting smoking in dispensing areas and open use areas and within 25 feet of outdoor <br /> 28 dispensing or open-use areas; <br /> Complaint for Injunction, Civil Penalties and Other Relief Page 7 <br />