Laserfiche WebLink
SA N J O A Q U I N Environmental Health Department <br /> COUNTY— <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Global Materials Management, LLC 1640 N Broadway Ave, Stockton August 26, 2016 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item # Remarks <br /> 102 HSC 25270.4.5(a) Failed to prepare a written SPCC Plan in accordance with CFR Part 112. <br /> This facility has an Aboveground Petroleum Storage Act(APSA) regulated shell capacity of 10,100 gallons. A Spill <br /> Prevention, Control, and Countermeasure (SPCC) Plan was not available on site. All facilities which have an APSA <br /> regulated shell capacity of 1,320 gallons or greater shall prepare a written SPCC Plan which meets all of the <br /> requirements of the 40 CFR Part 112. This plan shall be certified by a professional engineer in accordance with 40 <br /> CFR 112.3(d). Immediately prepare a SPCC Plan in accordance with 40 CFR Part 112, which that includes all <br /> aboveground petroleum storage containers 55 gallons or larger. Submit a copy of the Professional Engineer (PE) <br /> certified SPCC Plan to the EHD for review. (This copy will be returned to the facility after review.) A copy shall be <br /> maintained on site at all times. <br /> This is a Class II violation. <br /> 612 CFR 112.7(c) Plan failed to include secondary containment, diversionary structures, or equip to prevent discharge. <br /> No secondary containment was observed for the 180+ drums of used oil or the used oil storage in the filter <br /> compactor. A facility shall provide appropriate containment and/or diversionary structures or equipment to prevent a <br /> discharge. The entire containment system, including walls and floor, must be capable of containing oil and must be <br /> constructed so that any discharge from a primary containment system will not escape the containment system <br /> before cleanup occurs. Immediately provide adequate secondary containment for all aboveground petroleum <br /> storage containers larger than 55 gallons. <br /> This is a Class II violation. <br /> 618 CFR 112.7(e), 112.8(c)(6) Failed to conduct inspections or integrity tests or maintain records for 3 years. <br /> No inspections are being conducted on the 180+ drums of used oil or the used oil storage in the filter compactor. <br /> Inspections and testing shall be conducted on all aboveground liquid petroleum containers larger than 55 gallons, <br /> including the filter compactor and all 55 gallon drums of oil. Records of these inspections and tests shall be signed <br /> by the appropriate supervisor or inspector and kept on site with the Spill Prevention, Control, and Countermeasure <br /> (SPCC) Plan for a period of three years. Immediately begin necessary testing and inspections for all Aboveground <br /> Petroleum Storage Act regulated containers and maintain on site with the SPCC Plan. <br /> This is a Class II violation. <br /> 619 CFR 112.7(f)(1) Failed to train personnel on discharge prevention. <br /> Oil handling personnel were not trained. At a minimum, oil handling personnel shall be trained in the operation and <br /> maintenance of equipment to prevent discharges; discharge procedure protocols; applicable pollution control laws, <br /> rules, and regulations; general facility operations; and the contents of the Spill Prevention, Control, and <br /> Countermeasure Plan. Immediately provide this training to all oil handling personnel and submit a copy of the <br /> training log to the EHD. <br /> This is a Class II violation. <br /> FA0014999 PR0541223 SC001 08/26/2016 <br /> EHD 28-01 Rev. 11/07/2017 Page 4 of 7 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />