passed vacuum test. Please see attached work order dated 5/21/14. <br />Q Designated Operator will continue to perform a visual inspection and will address <br />issues if deficiencies found. <br />#405. The 87 vent line vacuum liquid sensor (S2) and the 87/91 vapor recovery line vacuum <br />(S3) failed when tested. The continuous monitoring system shall be maintained to detect <br />the entry of the liquid or vapor phase of the hazardous substance stored in the primary <br />containment into the secondary containment and to detect water intrusion into the <br />secondary containment. <br />Q The float on the 87 vent line vacuum liquid sensor (S2) was replaced during the <br />inspection. <br />u The 87/91 vapor recovery line vacuum (S3) was retested and passed on 5/16/14. <br />U Please see attached Monitoring Certification. <br />#201. According to the designated operator inspection report, alarms on April 25, 2013 was <br />due to a technician on site. No maintenance records were found on site for this date. <br />u Chevron contractor (SSS) was on site on 4/25/13 due to the Diesel line leak detector <br />repairs. Please see attached work service order <br />Please do not hesitate contacting me if you have any questions or concerns. <br />Sincerely, <br />Pauline Calalang <br />UST Compliance Coordinator <br />6001 Bollinger Cyn. Rd. L1193 <br />San Ramon, CA. 94583 <br />Tel: 925.842.1105/Cell: 707.315.4737 <br />Fax:: 1866.420.0335 (Attn: PNCP) <br />Disclaimer: This message may contain confidential information and is intended only for the <br />use of the parties to whom it is addressed. If you are not an intended recipient, you are <br />hereby notified that any disclosure, copying, distribution or use of any information in <br />this message is strictly prohibited. If you have received this message in error, please <br />notify me immediately at the telephone number indicated above <br />From: Stacy Rivera [EH] [mailto:srivera@sjcehd.com <mailto:srivera@sjcehd.com> ] <br />Sent: Friday, May 09, 2014 11:33 AM <br />To: Calalang, Pauline [CSI] <br />Subject: RE: Chevron 307709 <br />Attached are the inspection reports from the Underground Storage Tank (UST) and Hazardous <br />Waste Generator inspections conducted at 10858 Trinity Pkwy., Stockton on April 21, 2014. <br />Copies have also been mailed. I've attached a blank Return to Compliance Certification <br />form, as well. Please let me know if you have any questions. <br />Stacy Rivera, REHS <br />2 <br />