Laserfiche WebLink
Page 1 of 1 <br />SPILL/OVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Fill Riser Containment Sumps r <br />Fill Riser Containment Sumps are Present, but were Not Tested r <br />Test Method Developed By: r Spill Bucket Manufacturerto Industry Standard r Professional Engineer <br />(' Other (Specify): <br />Test Method Used By: r Pressure t ' Vacuum r Hydrostatic <br />r Other (Specify): <br />Test Equipment Used:LAKE E TEST <br />Equipment Resolution: ,_0.0625 in <br />Bucket Diameter: <br />Spill Box # <br />Tank 1 UNLEADED <br />Fill - Direct <br />12.00 <br />Spill Box # <br />Tank T-2 PREMIUM <br />Fill - Direct <br />12.00 <br />Spill Box # <br />Tank T-3 Diesel <br />Fill - Direct <br />12.00 <br />Spill Box # <br />Bucket Depth: <br />14.00 <br />14.00 <br />14.00 <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test <br />5 min <br />5 min <br />5 min <br />m i n <br />Test Start Time: <br />09:30:00 <br />09:30:00 <br />09:30:00 <br />Initial Reading (a,): <br />14.00 in. <br />14.00 in. <br />14.00 in. <br />Test End Time: <br />10:30:00 <br />10:30:00 <br />10:30:00 <br />Final Reading m,>: <br />13.75 in. <br />14.00 in. <br />14.00 in. <br />Test Duration: <br />1 hr <br />1 hr <br />1 hr <br />Change in Reading (a,a,(: <br />-0.25 In. <br />0.00 in. <br />0.00 in. <br />Pass/Fail Threshold or Criteria: <br />+/- 0.00 <br />+/- 0.00 <br />+/- 0.00 <br />+/ <br />Test Result: <br />Fail <br />Pass <br />Pass <br />Comments ? (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />reg s.b. failed at bad bottom o -ring at the drain. <br />WO: 2302101 <br />