Issue_Da = 4 <br />to -Au ust�X�0 <br />Veeder-Root <br />Secondary Containment Leak Detection (SOLD) <br />TLS-350/ProMax/EMC Console with Vacuum Sensors 857280-100, 200, 30x <br />PRESSURE/VACUUM INTERST TIAL MONITOR <br />Certification: <br />Certified as equivalent to European leak detection standard EN -13160, Class I leak detection system. <br />Operating Principle: <br />System uses vacuum generated by the turbine pump to continuously maintain a partial vacuum within the interstitial <br />space of double -walled tanks and double -walled piping. <br />System is designed to activate a visual and acoustic alarm, and optional turbine pump shutdown before stored <br />product can escape to the environment, and is capable of detecting breaches in both the inner and outer walls of <br />double -walled tanks and double -walled piping. <br />Alarm Condition: <br />System alarms when a liquid or air leak occurs which causes the interstitial vacuum to decrease (pressure to <br />increase) and the system js unable to maintain minimum vacuum. System will also alarm if liquid is detected in the <br />interstitial space, or if the vacuum level in the interstitial space decreases at a rate exceeding 85±15 liters/hour. <br />Applicability: <br />Underground double -walled tank, connected double -walled piping, and Aer connected interstitial spaces storing <br />gasoline, gasohol, diesel, heating oil #2, kerosene, aviation fuel, mottar. of ater. <br />Manufacturer's Specifications: t/ <br />Alarm will activate when interstitial vacuum decreases to�vacuu (3. "Hg}. <br />Default maximum vacuum level (pump -off pressure) is sl Gcu�i n (16. g), but can be set as low as <br />4 psi (8.2" Hg) if the monitored system requires that a'! Werlevel Qf vacuum be maintained. <br />The interstitial space shall be rated for the operattig vaGuu <br />�t of tike leak detector, regardless of temperature and <br />groundwater level fluctuations. t `� <br />Volume of monitored interstitial. space must7texile\ 8 3 or tanks and 10 m3 for piping. <br />When monitoring double -walled tanks a I Id sensor ust be located at lowest point of interstitial space. <br />Calibration: <br />Functional and operational afe s sou be performed in accordance with manufacturer's instructions. <br />Comments: <br />Interstitial space is tested con n�uou,S <br />System is connected to the inters#itial space by a single vacuum line. <br />Vacuum is generated by the turbine pump, and is measured and controlled by a vacuum sensor. <br />Veeder-Root Evaluator: Ken Wilcox Associates <br />125 Powder Forest Dr. Tel: (816) 443-2494 <br />Simsbury, Cf 06070-2003 Date of Evaluation: 06/09/2004 <br />Tel: 860-651-2700 <br />E-mail: dhalla@veeder.com <br />URL: www.veeder.com. <br />Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the <br />method or equipment_ Equipment should be installed and operated in accordance with all applicable laws and regulations. <br />