Laserfiche WebLink
SCOPE Do WORK <br />1.0 Scope of Work: <br />Page 4 <br />The scope of work consists of the removal and disposal <br />of one (1) 4000 gallon underground storage tank. <br />The tank will be purged of all remaining residues, and <br />these residues will be stored on site in 5 gallon D.O.T. <br />approved drums until they are hauled away for disposal <br />by a certified hazardous materials hauler. <br />The tank will be inerted with a minimum of 30 lbs of dry <br />ice per 1,000 gallons of tank capacity. More ice will <br />be added if necessary to displace the oxygen in the tank <br />to a concentration level below the OSHA approved lower <br />explosive limit. When this level is obtained the tanks <br />will be removed, and samples will be collected per the <br />approved work plan. <br />1.1 Responsibilities of Other Agencies Present: <br />a. The Environmental Health Department is responsible <br />for approval and inspection of procedures, including <br />tank removal, sample procurement and integrity of <br />work plan. <br />b" The Fire Department is responsible for inspection <br />relative to safe procedures and condition of tank <br />prior to removal. <br />