Laserfiche WebLink
SWRCB, January 2002 <br />7. UNDER -DISPENSER CONTAINMENT (UDC) TESTING <br />Page 5 <br />Test Method Developed By: <br />❑ <br />UDC Manufacturer ❑ Industry Standard X❑ Professional Engineer <br />Other (Specify) <br />Test Method Used: FI <br />❑ <br />Pressure F Vacuum Hydrostatic <br />Other (Spec) <br />Test Equipment Used: vplt <br />Equipment Resolution: .05gph <br />UDC Manufacturer: <br />UDC # ds 1 <br />western <br />UDC # <br />UDC # <br />UDC # <br />UDC Material: <br />fiberglass <br />UDC Depth: <br />25" <br />Height from UDC Top to Top of <br />Highest Piping Pentration: <br />loll <br />Height from UDCTop to Lowest <br />Electrical Pentration: <br />7 „ <br />Condition of UDC prior to testing: <br />good <br />Portion of UDC Tested: 1 <br />1211 <br />Does turbine shut down when <br />sump sensor detects liquid (both <br />product and water)?* <br />1Yes ❑No[:]N <br />Yes DNo❑N <br />EYes [:]No❑Nf <br />Yes [:]No❑NA <br />Turbine shutdown response time: <br />2-5 secs <br />Is system programmed for fail-safe <br />shutdown?* <br />Yes N N <br />❑ � <br />Yes N N <br />❑ ❑ <br />Yes N N <br />[:]Yes❑ � <br />Yes No <br />❑ ❑ l__f`� <br />Was fail-safe verified to be <br />operational?* <br />YLL]es �No�N <br />Yes �No❑N <br />Yes ❑No�N <br />Yes �No�T <br />Wait time between applying <br />pressure/vacuum/water and starting <br />test: <br />5 min <br />Test Start Time: <br />11:11 <br />Initial Reading (R1): <br />10.606 <br />Test End Time: <br />11:26 <br />Final Reading (RF ): <br />10.417 <br />Test Duration. <br />15 min <br />Change in Reading (R F - R1 ): <br />. 0 2 2 gph <br />Pass/Fail Threshold or Criteria: <br />. 05gph <br />Test Result: <br />Pass E Fail <br />ElPass El Fail <br />Pass Fail <br />E Pass 0 Fail <br />Was sensor removed for testing'? <br />X <br />Yes❑N NA <br />Yes No❑NA <br />EYesE]No[�]NA <br />L]Yes ❑No[]NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />Ye N NA <br />� � � <br />N NA <br />[:]Yes[:] � <br />Ye N NA <br />❑ � `ice <br />Yes N <br />❑ ❑ `9__I`� <br />Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />1 If the entire depth of the UDC is not tested, specify how much was tested. If the answer to anv of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />