SWRC13, January 2002 <br />4. TANK ANNULAR TESTING <br />Page of <br />Test Method Developed By: X Tank Manufacturer Industry Standard Professional Engineer <br />Other (Specify) <br />Test Method Used: -! Pressure X Vacuum I Iydrostatic <br />Other (Specify) <br />Test Equipment Used: Gast acuum Pump/Vacuum Gauge in I Ig. <br />Equipment RCSOIUtlon: s -30" 11" <br />r. <br />"Tank # 1 Tank # Tank # Tank # <br />Is Tank Exempt From Testing?' <br />No <br />Tank Capacity: <br />I OK <br />Tank Material: <br />Jacketed DW Steel <br />Tank Manufacturer: <br />K&T Steel <br />Product Stored: <br />Diesel <br />Wait time between applying <br />vacuum and starting test: <br />10 Minutes <br />Test Start Time: <br />12:45 <br />Initial Reading (Rj): <br />-7" Hg. <br />Test End Time: <br />1:45 <br />Final Reading (RF): <br />-7" Hg. <br />Test Duration: <br />1 Hour <br />Change in Reading (RF-Ri): <br />0" Hg. <br />Pass/Fail Threshold or Criteria: <br />No loss in Hg. <br />Test Result: <br />Pass <br />Was sensor removed for testing? <br />Yes <br />Was sensor properly replaced and <br />verified functional after testing? <br />Yes <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Tank has Annular Vent to Atmosphere. Annular Vent capped during Testing. <br />' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. {California Code of Regulations, Title 23, Section 2637(a)(6)) <br />