Laserfiche WebLink
VE <br /> SPOOITank Ins Inspection R EI <br /> p 2016 <br /> NCPA CTI, Lodi, CA 95240 <br /> Fig 2GIR <br /> ENVIRONMENTAL <br /> Discrepancies: HEA T�:0. , r;TVI_NT <br /> 1. Vegetation and dirt must be removed from beneath pipes and from the secondary <br /> containment. <br /> 2. Tank requires emergency vent unless forgiver) by the authority having jurisdiction. <br /> 3. Tank gauge calibration must be checked annually. <br /> 4. The secondary containment concrete shell must be repaired to prevent erosion and pest <br /> burrows. Cracks shall be sealed to prevent erosion. <br /> 5. Uncapped piping connections must be capped or blind flanged. <br /> John Strandberg PE,rwater uv a,rwater ue v.com 1-866-388-0404 2 1 P a g e <br />