Laserfiche WebLink
F. In -Tank Gauging / SIR Equipment: . Check this box if tank gauging is used only for inventory control. <br />Check this box if no tank gauging or SIR equipment is installed. <br />This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring. <br />Complete the followinq checklist: <br />Yes <br />No' <br />Has all input wiring been inspected for proper entry and termination, including testing for ground faults? <br />Yes <br />No` <br />Were all tank gauging probes visually inspected for damage and residue buildup? <br />Yes <br />No' <br />Was accuracy of system product level readings tested? <br />Yes <br />No` <br />Was accuracy of system water level readings tested? <br />Yes <br />No' <br />Were all probes reinstalled properly? <br />Yes <br />No' <br />Were all items on the equipment manufacturer's maintenance checklist completed? <br />In the Section H, below, describe how and when these deficiencies were or will be corrected. <br />G. Line Leak Detectors (LLD): ❑ Check this box if LLDs are not installed. <br />Complete the following checklist: <br />x Yes <br />No' <br />For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all <br />N/A <br />that apply) Simulated leak rate: 03 g.p.h.; 00.1 g.p.h ; ❑0.2 g.p.h. <br />Yes <br />x No' <br />Were all LLDs confirmed operational and accurate within regulatory requirements? <br />z Yes <br />No' <br />Was the testing apparatus properly calibrated? <br />x Yes <br />No' <br />For mechanical LLDs, does the LLD restrict product flow if it detects a leak? <br />N/A <br />Yes <br />No' <br />For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? <br />x N/A <br />Yes <br />No' <br />For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or <br />x N/A <br />disconnected? <br />Yes <br />No` <br />For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or <br />x N/A <br />fails a test? <br />Yes <br />No' <br />For electronic LLDs, have all accessible wiring connections been visually inspected? <br />x N/A <br />x Yes <br />No" <br />Were all items on the equipment manufacturer's maintenance checklist completed? <br />In the Section H, below, describe how and when these deficiencies were or will be corrected. <br />H. Comments: <br />Unable to test leak detector on T-1 Feeding the auto side due to turbin been out of service. <br />Monitoring System Certification Page of 12/07 <br />