Laserfiche WebLink
SWRCB,January 2002 Page 1 of <br /> 9. SPILL/O4)' <br /> RFILL CONTAINMENT BOXES <br /> Facility is Not E ui ed With Spill/Overfill Cooment Boxes ❑ <br /> Spill/Overfill Containment Boxes are Present, bul Were Not Tested ❑ <br /> Test Method Developed By: ❑Spill Bu4t Manufacturer ❑ Industry Standard X Professional Engineer <br /> ❑Other(Si' ify) <br /> Test Method Used: ❑Pressure':`: ❑Vacuum X Hydrostatic <br /> ❑Other (Spec) <br /> Test Equipment Used: MTS Mag Probe W/'I DII Meter Equipment Resolution: .001" <br /> Spill Box#1 41 Spill Box#2-87 Spill Box#3-Dsl Spill Box#4- <br /> Bucket Diameter: <br /> Bucket Depth: <br /> Wait time between applying <br /> pressure/vacuum/water and 10 Min. 10 Min. 10 Min. 10 Min. <br /> starting test: <br /> Test Start Time: 14:00 14:41 15:19 <br /> Initial Reading(R,): 0.000" _ 0.000" 0.000" 0.000" <br /> Test End Time: 14:24 15:05 15:43 <br /> Final Reading(RF): 0.000" 0.000" 0.000" <br /> Test Duration: 24 Min 24 Min 24 Min 24 Min <br /> Change in Reading(RF-R,): .000" , .000" .000" <br /> Pass/Fail Threshold or <br /> Criteria: +/- .004" +/- .004" +/- .004" +/- .004" <br /> Test Result: X Pass ❑F4 X Pass ❑Fail X Pass ❑Fail ❑ Pass ❑Fail <br /> Comments—(include information on repairs r4pde prior to testing, and recommended follow-up forfailed tests) <br /> a <br /> i; <br /> S.' <br /> f <br /> K <br /> t. <br />