Laserfiche WebLink
SWRCB,January 2002 Page (P of <br /> S. FILL RISt:R CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Contaiihrent Sumps ❑ <br /> Fill Riser Containment Sumps are Present,but ere Not Tested ❑ <br /> Test Method Developed By: ❑Sump MAnufacturer ❑Industry Standard X Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑ Pressure ❑Vacuum X Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: MTS Mag Probe W/TDIJ Meter Equipment Resolution: .001" <br /> Fill Sump#1-91 Fill Sump#2-87 Fill Sump#3-Dsl Fill Sump#4- <br /> Sump Diameter: 43:" 42" 42" <br /> Sump Depth: 3': " 38" 43" <br /> Height from Tank Top to Top of 2 " 19" 18" <br /> Highest Piping Penetration: _ <br /> Height from Tank Top to Lowest <br /> Electrical Penetration: 17" 17" <br /> Condition of sump prior to <br /> testing: G.:,,d Good Good <br /> Portion of Sump Tested 2;:" 21" 20" <br /> Sump Material: Fibe Jass Fiberglass Fiberglass <br /> Wait time between applying <br /> pressure/vacuum/water and 10 Min. 10 Min. 10 Min. 10 Min. <br /> starting test: <br /> Test Start Time: 14' 14:41 15:19 <br /> Initial Reading(R,): 0.000" 0.000" 0.000" 0.000" <br /> Test End Time: 1411, 15:05 15:43 <br /> Final Reading(RF): O.Lj�O" 0.002" 0.000" <br /> Test Duration: 24"Ain 24 Min 24 Min 24 Min <br /> Change in Reading(RF-R,): .(1XQ" -.002" .000" <br /> Pass/Fail Threshold or Criteria: +/-'.'!04" +/- .004" +/- .004" +/- .004" <br /> Test Result: X Pass:; ❑Fail X Pass ❑Fail X Pass ❑Fail ❑ Pass ❑Fail <br /> Is there a sensor in the sump? X Yes _? No X Yes ❑No X Yes ❑No ❑Yes ❑No <br /> Does the sensor alarm when <br /> either product or water is X Yes l,o ❑NA X Yes ❑No ❑NA X Yes ❑No [INA ❑Yes ❑No ❑NA <br /> detected? <br /> Was sensor removed for testing? X Yes !o ❑NA X Yes ❑No ❑NA X Yes ❑No [INA ❑Yes 0 No ❑NA <br /> Was sensor properly replaced and <br /> verified functional after testin ? X Yes Wo ❑NA X Yes ❑No ElNA X Yes ❑No ❑NA ❑Yes EINo [INA <br /> Comments—(include information on repairs;i 4ode prior to testing, and recommended follow-up for failed tests) <br /> 4 <br /> ft. <br /> i <br />