Laserfiche WebLink
MAR 0 4 2015 <br /> D.Resulbs of Testing/Seryidng <br /> Software Version Installed: 329.01 F-WRONMENTM <br /> Complete the following checklist: <br /> IT Yes No' s the audible alarm operational? <br /> • Yes No* s the visual alarm operational? <br /> • Yes No* Nere all sensors visually inspected,functionally tested,and confirmed operational? <br /> • Yes No- Mere all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere witt <br /> heir properoperation? <br /> • Yes No• f alarms are relayed to a remote monitoring station,is all communications equipment(e.g.modem)operational? <br /> N/A <br /> • Yes No* or pressurized piping systems,does the turbine automatically shut down if the piping secondary containment monitoring <br /> N/A stem detects a leak,fails to operate,or is electrically disconnected?If yes:which sensors initiate positive shut-down?(Check <br /> all that applyfV Sump/Trench Sensors; r Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failure/disconnection?O Yes; r No <br /> IT Yes r No. or tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e.no mechanical overfill <br /> revention valve is installed),is the overfill warning alarm visible and audible at the tank fill point(s)and operating properly?If <br /> N/A at what er<ent of tank capacity does the alarm trigger?90% <br /> • Yes* No Nas any monitoring equipment replaced?If yes,identify specific sensors,probes,or other equipment replaced and list the <br /> anufacturer name and model for all replacement parts in Section E below. <br /> Yes* • No as liquid found inside any secondary containment systems designed as dry systems?(Check all that apply) <br /> ProducC r Water.If es describe causes in Section E below. <br /> • Yes NO Nas monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> • Ves No- <br /> .s all monitoring equipment operational per manufacturers specifications? <br /> *In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E.Comments: <br /> light bulb on e#alarm was replaced.all passed. <br /> Monitoring System Certification Page 2 of 3 12/07 <br />