Laserfiche WebLink
Inspection Notes <br />ASW SPO01 Inspection, 25 October 2016 <br />F-24 Jct Fuel Storage Tank, 20,WO Gal. <br />Stockton AASF <br />2000 Stimson Rd , Stockton, CA 95206 <br />Larry Lsyuerra, STI Inspector #AS I'-1693 <br />Tank is steel AST, double wall, horizontal, 10 8" diameter x 39' long <br />Contents; F-24 Jet Fuel <br />Legend for Plan View of AST and containment <br />A. Welded stainless steel Piping and appurtenances <br />Page 1?3 <br />B. Steel tank saddles, 2 ea., 22" wide and 3 ft height up side-wall of tank. <br />Saddle height is 4" from concrete pedestal to bottom of tank. Each <br />end of saddle has 3 ea. V dia. anchor bolts, so 12 anchors total <br />C. 2" containment drain line with locked valve. <br />U. Bottom of tank is 12" above the concrete slab and 4" above the concrete <br />pedestals <br />Legend for Plan View of AST <br />1. Secondary tank leak detector sensor inside 2" gale. pipe <br />2. Secondan tank normal vent <br />3. 4" locked cap <br />3. 2 -primary tank normal vent <br />5 4" connection for high level alarm <br />6. Primary tank emergency vent, 12" <br />7. Bolted manway, 24" <br />S. Cap, 10", possibly normal %-ent <br />9 & 10. 3" plug <br />I 1 & 12. 3" stainless steel pipe connection <br />14 <br />