Laserfiche WebLink
Inspection Notes <br />1 Site is fenced and secured 24-7 <br />2. Tank is grounded_ <br />21z <br />3 Cracks at concrete slab have satisfactorily hien filled with caulking sealant. <br />4. Tank coating is in good condition. Stairway and landing in good condition. <br />5. UTG readings (mal); 6.5, 6.5, 6.5, 6.51 6.5, 6.8, 6.5, 6.5 At east end of tank, <br />four readings taken- all 8.5 mm. <br />6. Operator indicated tank is 12 NTS. old. Viceder — Root level indicator;'control <br />shuts down pumping with high level alarm. These is also a low level alarm to <br />indicate that the tank needs filling to minimize tank moisture build-up. <br />7 Taa- manufacturer; Trusco Wank Inc., Fresno, CA, SIN 105350 <br />8. 'Tank model is "SuperVault MH" (1Vtulti Hazard), and is SwRI listed I.I. No. <br />960401-01-03 and per the label, "Complies with S%vRi test procedure 95-03 <br />and 93-01." "This product has been listed after passing a 4 -hour Fire Exposure <br />Test, a Hose Stream Resistance Test, a Projectile Penetration Test, a Heavy <br />Vehicle Impact Test. an Environmental Exposure Evaluation, and an <br />additional 2 -hour Fire Exposure Test king the same fully assembled test tank <br />for all tests." <br />9. Tank is .AST Category 1. <br />15 <br />