Laserfiche WebLink
AFFORDA-TE$T AST TANK TEST <br /> 416 2°d Street Galt,Ca. 95632 <br /> 209 744-0112 Fax 209 744-0116 PRIMARY & ANNULAR <br /> Site: MARTIN BROWER TRUCKING Test Date: 7/20/2011 <br /> Address: 4704 FITE CT. <br /> City: STOCKTON, CA Equipment: NITROGEN, GAUGES, <br /> Test Method Developed By: Tank Manufacturer Industry Standard X Professional Engineer Other S eci <br /> Test Method Uses: Pressure XXX Vacuum Hydrostatic Other(Specify): <br /> Measuring Equipment Used for Testing:STANDARD DIGITAL PSI GAUGE <br /> Tank#1 Tank#1 Tank#2 Tank#2 <br /> ® PRIMARY ❑ PRIMARY ® PRIMARY ❑ PRIMARY <br /> ❑ ANNULAR ® ANNULAR ❑ ANNULAR ® ANNULAR <br /> Tank Capacity: 10,000 200 10,000 200 <br /> STEEL STEEL STEEL STEEL <br /> Tank Material: <br /> DIESEL 2 DRY DIESEL 2 DRY <br /> Product Stored: <br /> Wait time between applying <br /> Pressure/vacuum/water and starting SET UP TIME -- -- -- <br /> test: <br /> 1230 1240 1320 1335 <br /> Test Start Time: <br /> 3.010 3.052 3.031 3.042 <br /> Initial Reading Ri): <br /> 1330 1340 1420 1435 <br /> Test End Time: <br /> 3.004 3.048 3.032 3.041 <br /> Final Reading(Rf): <br /> HOUR HR HR HR <br /> Test Duration: <br /> -.006 -.004 +.001 -.001 <br /> Change in Reading Rf-Ri : <br /> -.01 -.01 -.01 -.01 <br /> Pass/Fail Threshold: <br /> PASS PASS PASS PASS <br /> Test Result: <br /> N/A N/A N/A N/A <br /> Was sensor removed for testing? <br /> Was sensor properly replaced after <br /> testing? I N/A N/A N/A N/A <br /> Comments AFTER TESTING STUCK ANNULAR SPACE TO CHECK FOR ANY LIQUID <br /> INTRUSION, THERE WAS NONE SYSTEM IS DRY AND CLEAN. ALL PASS! <br /> Technician: ZANE NIMMO <br /> OTTL#041676 ICC 5263322-UT ICC 5263322-U3 <br /> Oregon UST Service#26755 Oregon UST Tank Tightness#26756 <br /> Nevada UT-2206 <br /> Signature: <br /> Date: 7/20/11 <br />