Laserfiche WebLink
711 CFR 112.8(c)(6) Failed to perform scheduled tank tests or inspections by appropriately qualified personnel. <br /> The 20,000 gallon, 12,00 gallon and 10,000 gallon tanks were not tested on schedule by a certified SP-001 <br /> inspector. The SPCC plan calls for formal inspections by a certified SP-001 inspector every 20 years.The age of the <br /> tanks could not be determined at the time of the inspection. Each aboveground container shall be tested and <br /> inspected for integrity on a regular schedule and whenever repairs are made.The qualifications of personnel <br /> performing tests and inspections,frequency and type of testing and inspections that take into account container <br /> size,configuration,and design shall be determined in accordance with industry standards. Examples of these <br /> integrity tests include,but are not limited to: visual inspection, hydrostatic testing, radiographic testing, ultrasonic <br /> testing,acoustic emissions testing,or other systems of non-destructive testing. Comparison records and other <br /> records of inspections and tests must be maintained on site. Immediately provide evidence that the tanks are not <br /> yet due for formai inspections or conduct the necessary testing and submit a copy of the test results to the EHD or <br /> provide equivalence as allowed by CFR 112.7(a)(2). <br /> This is a Class II violation. <br /> Tank inspections were completed on December 7,2018 by Gary Reeves, LLC(Certified Steel Tank Institute Level I& <br /> Level 11 Tank System Inspector). No defects were found. Please see attached. <br /> 11396 NORTH HWY 991 LODI,CALIFORNIA USA 95240-68991(800)692-34571 FAX(209)931-6156 www.titrucking.com <br />