RECEIVED <br />JUL 2 8 2014 <br />ENVIRONMENTAL HEALTH <br />SWRCB, January 2002 DEP, Tq_ . <br />7. UNDER -DISPENSER CONTAINMENT (!TDC) TE, STING <br />Test Method Developed By: <br />❑ UDC Manufacturer <br />❑ Other (Spec) <br />❑ Industry Standard X Professional Engineer <br />Test Method Used: <br />❑ Pressure <br />❑ Other (Specif) <br />❑ Vacuum <br />X Hydrostatic <br />_ <br />Test Equipment Used: TS -STS icon sump test system <br />Equipment Resolution: <br />UDC Manufacturer: <br />UDC # 25 <br />UDC #26 <br />UDC #27 <br />UDC #27s <br />BRAVO BRAVO BRAVO <br />BRAVO <br />UDC Material: <br />FIBERGLASS <br />FIBS; ASS <br />FIBERGLASS <br />FIBERGLASS <br />UDC Depth: <br />30" <br />30" <br />30" <br />30" <br />Height 8-om UDC Bottom to Top <br />of Highest Piping Penctradun: <br />I2" <br />19.11 <br />12" <br />[2" <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: <br />0 <br />0 <br />0 <br />0 <br />_ <br />Condition of UDC prior to <br />testing: <br />CLEAN <br />CLEAN <br />CLEAN <br />CLEAN <br />Portion of UDC Tested <br />20" <br />20" <br />20" <br />20" <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />product and water)?` <br />❑ Yes ONo XNA <br />❑ Yes ❑ No XNA <br />❑Yes ONo XNA <br />n Yes ONo XNA <br />Turbine shutdown response time <br />NIA <br />NIA <br />NIA <br />N/A <br />Is system programmed for fail- <br />safe shutdown? <br />❑Yes F) No XN1A <br />❑Yes ONo XN/A <br />❑Yes 0 N XNIA <br />❑Yes ONo XN/A <br />Was fail-safe vetiftedtobe <br />operational? <br />❑Yes ONo XN/A <br />❑Yes ONo XNIA <br />❑Yes ONo XN/A <br />❑Yes ONO XN/A <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test <br />15 min <br />15 min <br />15 min <br />15 min <br />_— <br />Test Start Time: <br />2 PM <br />2 FM <br />2 PM <br />2 PM <br />Initial Reading (Bq): <br />7.3726 <br />6.2513 <br />3.0123 _ <br />5.7871 <br />Test End Time: <br />2;42 PM <br />2:22 PM <br />2:22 PM <br />2:22 PM <br />Final Readies RF : <br />7.3729 <br />6.2500 <br />3.0114 <br />57882 <br />Test Duration: <br />15 ruin <br />15 min <br />15 min <br />15 min <br />Change in Reading F Rt): <br />.0003+ <br />.0013 <br />.0008 <br />+.001 <br />Pass/Fail Threshold or Criteria: <br />.002 <br />.002 <br />.002 <br />.002 <br />Test Result: <br />X PASS ❑71an <br />X.1_'Ass ❑Fruit <br />X PADS ONail <br />R Pass QFail <br />Was sensor removed for testing? <br />XYes 0 N 0 N <br />XYes ONo ❑NA <br />XYes ONo ❑NA <br />XYes ONo DNA <br />Was sensor properly replaced and <br />verified functional after testut '1 <br />XYes ONo DNA <br />XYes ONo ONA <br />XYcs ONo DNAX <br />Yes DNo DNA <br />Comments— (include in formation on repairs made prior to testing and) econ»tiended folloia,-vp for• failed testa) <br />SENSOR ALARM ONLY <br />If the entire depth of the UDC is not tested, specify how much was tested. If the answer to an of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See S WRCB LG -160) <br />