Transmission Contact Switch <br />• Automatic telephone dialer: <br />❑ Typically requires only a contact switch to activate <br />dialing function. <br />❑ Is plugged (or wired directly) into an electrical out- <br />let for power source. <br />• Dialer power source is not supplied by control panel. <br />❑ With power to control panel, normally -closed con- <br />tacts are at terminals 3 and 4. <br />❑ Terminals will open - providing the switching mecha- <br />nism to activate dialer - when control panel goes <br />into alarm mode. <br />Model SBOOr1C Shown <br />4 <br />Power Cirourt s.r.°r c.a.t <br />(To 120 Vola AQTo Ground Connor (To Senior Ass --&O <br />Swrtch Ctrewt <br />Power Cwcwt Autw,y0e i Teftfa <br />(TO 120 V01t7 AC) PhorW payer ler <br />Power Source Switch <br />Do not place intrinsically safe sensor <br />AWARNING wiring in the same conduit as non - <br />intrinsically safe wiring. <br />CAUTION: Place wiring in watertight conduit and junc- <br />tion boxes (to maintain leak detection capability). <br />• Typical wiring diagram is provided for accessories re- <br />uiring power such as light beacon. <br />Contacts (see Figure B, page 30) can provide 120 <br />volts AC. <br />❑ Optional warning device must be rated for 300 watts <br />or less. <br />D5. Alarm Bell Silence Button <br />• Depress Bell Silence Button on control panel to silence <br />alarm bell. <br />❑ The alarm bell will activate again if second alarm <br />condition occurs. <br />D6. Normal Operation <br />• If"NORMAL" light is continuously illuminated, it means <br />liquid level is in normal range. <br />18 <br />• Inner and outer walls are leak -free if liquid level in reser- <br />voir is stable. <br />• Liquid level in reservoir will fluctuate as the tempera- <br />ture of incoming stored product changes. <br />• Reservoir is designed to provide adequate capacity for <br />normal thermal expansion and contraction. <br />D7. Testing and Maintenance <br />Important: Check control panel warning system at least <br />once per year. <br />• Depress "TEST BUTTON" switch on front of control <br />panel to verify that each internal circuit is operational. <br />❑ This does NOT test operation of monitoring sensors. <br />• Use troubleshooting guide (See Figure A, page 29) to <br />diagnose faulty circuit in control panel. <br />• Contact Fluid Containment Field Service for control Panel <br />replacement parts. Phone number listed on page 2. <br />D8. Leak Detection <br />• In the unlikely event reservoir totally drains: <br />❑ Control panel alarm will activate. <br />❑ Warning light will illuminate. <br />❑ Alarm bell will sound. <br />❑ Transmission contacts will activate any accessory <br />alarm device. <br />• Alarm bell can be silenced by pushing Bell Silence But- <br />ton. <br />❑ "WARNING" light will remain on. <br />❑ "NORMAL" Light is off- <br />0 <br />ff <br />• See section C8 - Reservoir Leak Detection. <br />D9. Control Panel False Alarms <br />• Occur when panel goes into alarm mode, but reservoir <br />liquid level is still in normal range. <br />• Typically result from failure of an electronic component <br />inside control panel. <br />• To maintain the "NORMAL" condition: <br />❑ All electronic components must function properly. <br />❑ Any electrical component failure will result in an <br />"ALARM" condition. <br />Important: Refer to troubleshooting guide on page 29 <br />to identify specific problem. <br />