i • <br /> API 653 Out-of-Service Inspection Report <br /> for <br /> J.R. Simplot Inspection <br /> Tank No. 8 August 27-28,2008 <br /> Lathrop, CA Page 9 of 54 <br /> SUMMARY, REPAIR RECOMMENDATIONS AND POST-REPAIR FINDINGS <br /> (CONT'D.) <br /> FIXED ROOF: The fixed roof coating is weathered and has water 1 dirt streaking <br /> present. In addition, new patch plates have been installed and are not coated. <br /> Consideration should be given to re-coating the roof in the near future. <br /> A new 6-inch stainless steel top fill nozzle was being installed at this time. <br /> ADDITIONAL COMMENTS: The next in-service external inspection should be <br /> conducted no later than August 2013 (5-year interval - ref. API 653, Para. 6.3.2.1). <br /> APIRPTNE.00T REV 2 26280304!&.COO 9!25/2008 10:09 AM <br />