Laserfiche WebLink
SWRCB,January 2002 Page of' <br /> 7. UNDER-DISPENSER CONTAINMENT-("C) TESTING <br /> Test Method Developed By: ❑UDC Manufacturer Industry Standard X Professional Engineer <br /> 0 Other(Speck) II <br /> "fest Method Used: 0 Pressure Vacuum X Hydrostatic II <br /> I Other(Specify) <br /> Test Equipment Used: Caldwell level Change Indicator Equipment Resolution: .002 it <br /> Y , �- <br /> UDC# 17&18 UDC# 19&20 UDC#21 m ' UDC#21s&22m <br /> UDC Manufacturer: Environ Environ Environ Environ II <br /> UDC Material: Pol Plastic PolyPlastic PolyPlastic Poly Plastic l <br /> _.�_�._ _ <br /> ........... <br /> UDC Depth:..._...._..__—..._ 30" —_ 30" 28" —._— 28" <br /> Height from UDC Bottom to Top l0" 10" 8" 8" <br /> i of Flighest Piping Penetration. <br /> Height from UDC Bottom to $" 8 ''/a" 4" 4" I <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Dry Dry Dry Dry <br /> testing: _ <br /> Portion of UDC Tested- Water Lever 15" Water Level 17" Water Level 12" Water Level 12" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both I X Yes No 1]NA X Yes No 0 NA X Yes No DNA X Yes No i'NA <br /> product and water). <br /> Turbine shutdown response time Not Alarmed Not Alarmed Not Alarmed Not Alarmed <br /> r is s stem programmed for fail- <br /> �' y p b X Yes 01 No DNA X Yes D No DNA X Yes D No DNA X Yes 0 No L?NA <br /> safe shutdown. <br /> ......._...... <br /> I Was fail-safe verified to be r Yes X No NA Dyes X No O NA Dyes X No DNA Dyes X No f-7 NA <br /> operational? <br /> Wait time between applying 5 Minutes 5 Minutes S Minutes S Minutes <br /> water and starting test <br /> _....._.. ..._......_ —.—... <br /> -Start Time: 8:20 8:55 1 1:35 11:40 <br /> initial Reading(R,): .001 .001 I .001 .001 <br /> Test End Time: 8:50 9:25 12:05 12:10 I <br /> Final Reading(RF): .001 .001 .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading(RF-Ri): 0 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005/30 Minutes 1 .005/30 Minutes I 005/30 Minutes <br /> Test Result: X Pass 0 Fail X Pass 0 Fail X Pass 0 Fail X Pass ❑ Fail_ y <br /> Was sensor removed for testing? X Yes 1jNo DNA X Yes 0No 0 NA X Yes D No 0 NA X Yes Ll No NA <br /> Was sensor properly replaced and X Yes C No 0 NA X Yes 'E'No NA X Yesr- <br /> -1 No F!NA I X Yes I.No NA <br /> verified functional after testing`? <br /> Comments—(include information on repairs made prior to testing, and recommendedollotiv_up or failed tests,) <br /> If the entire depth of the UDC is not tested,specify how much was tested. If the answer to as of the questions indicated with an <br /> asterisk(*) is"NO"or"NA", the entire UDC must be tested. (See SWRCB LG-160) <br />