Laserfiche WebLink
0 <br /> SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manufacturer U Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure X Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauge in Hg. Equipment Resolution:-%:"x-30"Hg. <br /> Tank#1,2&3 Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' No g. - <br /> Tank Capacity: 20K split 11/5/4 <br /> Tank Material: Glass/Steel <br /> Tank Manufacturer: Trusco JLL <br /> Product Stored: 87/91/Diesel p 9 <br /> Wait time between applying <br /> vacuum and starting test: 30 Minutes - <br /> Test Start Time: 10:25 <br /> Initial Reading(R,): -10 Hg. <br /> Test End Time: 12:25 <br /> Final Reading(RF): -10 Hg. <br /> Test Duration: 2 Hours <br /> Change in Reading(RF-R,): 0 Hg. <br /> Pass/Fail Threshold or Criteria: No Loss in Hg. <br /> Test Result: Pass <br /> Was sensor removed for testing? Yes <br /> Was sensor properly replaced and <br /> verified functional after testing? Yes <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up forfailed tests) <br /> 20K Split Compartment Tank, Ilk 87,5K 91& 4K Diesel. SingleAnnularl <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23, Section 2637(a)(6)) <br />