Laserfiche WebLink
4 <br /> 1994 UNIFORM FIRE CODE 7902.1.32-7902.1.7,4.4 <br /> EXCEPTIONS; 1.Tanks of 300(tanens(1175.514 opacity or Jess located on private properly and used <br /> for heating and cooking fuels in single-family dwelling . 1?t' <br /> 2.Tanks located underground. <br /> 7902.1.4 Sources of Ignition. Smoking and open fl es are prohibited in storage areas.See also <br /> . ' Section 7901.10. <br /> 7902.15 Explosi0r control. T:'xplosion contrul, icuivalent protection devices or suppression ;_vt_: <br /> , systems,or a barricade shall be provided in accordartf with the Building Code when Class I liquids <br /> _. xempt atm ants,or where explosive vapor-air mixtures ' <br /> are stored inside buildings in excess of the e <br /> could develop under normal operating conditions. i <br /> :fir'. �•� P - <br /> �;; EXCErrm:Class I-B and I-C liquids when pro,ided with continuous ventilation at the rate set forth <br /> in Section 8003.1.8. - <br /> 'f++' See also Sections 7902.5.11.7,7902.5.L2.7.7903. 3,4.3 and 7903-2.3.5.3.1 <br /> ;;2�y', _ <br /> 7902.1.6 Separation from incompatible material and accumulation of combustibles. Stor- <br /> . age of flammable and combustible liquids shall be sel arated from incompatible hazardous mated• <br /> 't= als in accordance with Section 8001.9.8. <br /> Ya. <br /> yr Grass;weeds;combustible materials;and wash Cl ss L U and III-A liquids shall not be accumu- <br /> laced in an unsafe manner at a storage site. <br /> --� 7902.1.7 Abandonment and status of tanks. <br /> «' <br /> 7902.1.7.1 General, 'tanks taken out of service asg result of a property's being abandoned or its <br /> use being changed shall be removed or abandoned in: lace in accordance with Section 7902.1.7.2.3 <br /> or 7902.1.7.3.3.The time schedules stipulated shall of apply. "'Al <br /> . ' In other cases, tanks taken out of service shall be safeguarded or removed n accordance with :�': <br /> 10 <br /> Section 7902.1.7. <br /> 7902,1.7.2 Underground tanks. <br /> "• ;< _ 7902.1.7.2.1 Temporarily out of service. Underg ound tanks temporarily out of service shall <br /> . . '� have the fill line,gage opening,vapor return and pur kpi connection secure against tampering.Vcnl <br /> .'.. ' lines shall remain open and be maintained in accord ancc with Sections 7902.1.10 and 7902.2.6. <br /> 7902.1.7.2.2 Out of service 90 days. Underground Lariks not used for a period of 90 days shall be <br /> safeguarded in accordance with the following or rery re: oved in accordance with Section 7902.1,7.4: <br /> =; 1. Flammable or combustible liquids shall be=iovrd from the tank, <br /> .a 2. AllP•P• 8 l m , including fill line, gage opening, vapor return and Pump connection, shall be <br /> capped or plugged and secured from tampering, an <br /> ?x; 3. Vent lines shall remain open and be maintaineJ in accordance with Sections 7902.1.10 and ' <br /> .�. 7902.2.6. ,•t2' <br /> ' 7902.1.7.2.3 Underground tanks out of service;for one year. Underground tanks which have <br /> been out of service for a period of one year shall bb moved from the ground in accordance with <br /> _`• Section 7902.1.7.4 and the she shall be restored in an approved manner.When the chief determines .'W� <br /> --'si that the removal of the tank is not necessary,abandi nment in place is allowed, ' <br /> T l <br /> •?` �-- 7902.1,7.2.4 Tanks abandoned in place. Tanks a doped in place shall be abandoned as fol- <br /> .� g <br /> lows_ -,}, . <br /> 1. Fiammable and combustible liquids shall bear moved from the tank and connected piping, ' <br /> 2. The Suction,inlet,gage, vapor return and vap r tines shall be disconnected, TT <br /> 3. The tank shall be filled completely with an in rt solid material approved by the chief, <br /> 4. Remaining underground piping shall be capped or plugged,and <br /> 5. A record of tank size, location and date of aW donment shall be retained. _ <br /> z <br /> 1-245Arlin <br /> .64 <br /> ar 410 7 <br /> LVJ'd X558+Lz6+50c :.�31N30 1IW'c'.d Noll-GC1S ct%:VT 955L-5�—i1CPl <br />