| 
								    I I i 
<br />SEE DET. B BELOW 
<br />SIEFL PLATES UNDER EACH 
<br />OPENING BY TANK MANUFACTURER -" VERIFY will TANK MFG 
<br />15,000 GAL. FIBERGLASS TANK SECTION 
<br />G 
<br />z 
<br />to 
<br />a'I 
<br />I 
<br />�,m 
<br />SII 
<br />4I 
<br />Y O 
<br />L 
<br />1 
<br />elsealp 
<br />--'- 
<br />-1 
<br />I 
<br />C) 
<br />n 
<br />� tJ 
<br />L,a 
<br />lam' 
<br />rg 
<br />T 
<br />6T 
<br />i 
<br />6i 
<br />IL 
<br />Z 
<br />x, 
<br />a - 
<br />E 
<br />H 
<br />I 
<br />l 11 
<br />° 
<br />b 
<br />oiu 
<br />_7 
<br />_I 
<br />C1 
<br />u 
<br />I 
<br />I 
<br />F, 
<br />a 
<br />v 
<br />Y 
<br />I -------4" 
<br />ALUMINUM FILL TUBE 
<br />W/POSITIVE. Sill 
<br />I 
<br />I 
<br />MONITORPROBE TO LOW 
<br />' 
<br />END OF i ANK. 
<br />$ 
<br />n 
<br />1r 
<br />I 
<br />II 
<br />I I 
<br />1 
<br />SLOPE TANK 1" IN 10' 
<br />DOWN TOWA' DS FILL END 
<br />- 
<br />11 
<br />I I i 
<br />SEE DET. B BELOW 
<br />SIEFL PLATES UNDER EACH 
<br />OPENING BY TANK MANUFACTURER -" VERIFY will TANK MFG 
<br />15,000 GAL. FIBERGLASS TANK SECTION 
<br />G 
<br />z 
<br />�/- 
<br />' I - 
<br />I ---4" ALUMrUM FILL TUBE W/POSITIVE SHUT OFF 
<br />I �r 
<br />MONITGRIPROBE TO LOW 
<br />I END OF ANK. 
<br />11 
<br />II 
<br />III 
<br />1 
<br />I I 
<br />SLOPE TANK 1" IN 10' 
<br />I DOWN TOAA DS FILL ENO 
<br />�. Id 1 1 
<br />STEEL PLATES UNDER EACH 
<br />OPENING BY TANK MANUFACTURER-' 
<br />MIN. 
<br />VERIFY W/ TANK MFG, 
<br />20,000 GAL. FIBERGLASS TANK SECTION 
<br />SCALE: 1/4" . V-0" 
<br />U) EV XULU, la 
<br />TUBE 
<br />OF FIBERGLASS OVERLAY 
<br />STEEL PLATE 
<br />7 
<br />--PEA GRAVEL 
<br />BACKFILL 
<br />2,p 
<br />\ 41. 
<br />fi YI� 
<br />SEE SET. B BELOW 
<br />I I 
<br />I I 
<br />I I 
<br />I I 
<br />I I 
<br />PEA GRAVEL 
<br />BACKFILL 
<br />LJ 
<br />1 1 k 
<br />- 
<br />MIN. 
<br />- --PUMP 
<br />TUBE 
<br />4" 
<br />`-- STEEL PLATE 
<br />DE`t &5L B 
<br />MIN. 
<br />SPECIFICATIONS 
<br />1.3 EXCAVATION AND BACKFILL: 
<br />A. EXCAVATION; If unexpected water condition or rock is encountered, immediately contact the 
<br />Owner Rep. for instructions before proceeding with the excavation. 
<br />B. TANK HOLE SIZE IN STABLE SOIL: Size excavation perimeter to allow 36" minimum between tanks 
<br />antl 24" minimum between tank sides and end caps and the wall of the tank hole, 
<br />C. TANK HOLE SIZE IN UNSTABLE SOIL: 
<br />1. Unstable soil is defined as having less than 750 lbs./sq. 1l. cohesion, as calculated from on 
<br />unconfined compression test, or soils with an ultimate bearing capacity of less then 3,500 
<br />lbs./sq.ft Loose sand, muck, bog, peat, swamp or landfill where soil is soft are generally 
<br />considered unstable sails. 
<br />2. Size excavation perimeter to allow 36" minimum between tanks and a minimum of half the tank 
<br />diameter between the lank sides/end caps and the wall of the lank hole. 
<br />rubric lie hole f FRP tanks in soil, 
<br />J. Filter abrl- will be used to n tank oil or R ll s unstable 
<br />4. Permanent o shoring may be used la stabilize the walls of the Conk hole, le the discretion of the 
<br />Contractor and/or Owner Rep. If permanent shoring is used, fallow "Stable Sail" size criteria. 
<br />Refer to "Alternate Backfill Materials", below. 
<br />D. DEPTH OF TANK HOLE. 
<br />1. Contractor is responsible for establishing the tank hole depth, considering the length of piping 
<br />runs, to the pump blocks and vent risers, pipe burial depth, yard slope and the following criteria; 
<br />(Measure at the Remove Pump opening), 
<br />o. FRP: The minimum depth of cover is 4'-0" and the maximum is 7'-0". 
<br />E, SAFETY REOUIRE.MENT: 
<br />No person shall enter a tank hole excavation below the 5 ft. deep level unless the walls are shored 
<br />or side sloped as prescribed by current OSHA regulations. No exceptions. State or local requirements 
<br />that are more restrictive than Company specifications are to be adhered to as though specified in 
<br />Company specifications. The Contractor is responsible for any design, materials, equipment, permits, 
<br />etc., for shoring or side sloping a hole. 
<br />F. FILL AND BACKFILL: 
<br />All fill material shall be of granular nature, free train vegetation and extraneous material. Owner 
<br />Repshall inspect and approve the material before it is spread Spread material in lifts not to exceed 
<br />12 inches and tamp thoroughly, when required by local code, Contractor shall provide a compaction 
<br />lest far certification of fill. 
<br />1.4 BALLAST 
<br />A. MATERIALS 
<br />Water is to be used as a ballast under all conditions where ballost is required. 
<br />B. DRY HOLE CONDITION: 
<br />Tonks, with backfill to lop of tanks, must be ballasted if there is any chance that surface or 
<br />subsurface water will enter the lank hole to a depth of 23" or greater above the bottom of the 
<br />tanks. 
<br />C. WET HOLE CONDITION; 
<br />Aie mpt to pumpwater from the tank hole to maintain a "Dr Hole Condition". If unable to obtain 
<br />o 'Pry Hole Condition",Owner Rep. n "l be and be and will p!ermine the course of action h ebe 
<br />, 
<br />followed, Install filter fabric, lie -down "logs" and bedding as specified elsewhere. Set tank in hale, 
<br />partially fill with water until it sinks firmly on the bed. Use only enough water to behest tank until 
<br />backfill is to top of tonk. After backfill to top of tank, fill tank with water until completion of 
<br />instolletion. 
<br />CAUTION - BALLAST LEVEL MUST NEVER EXCEED WATER OR BACKFILL LEVEL IN THE HOLE 
<br />DURING INSTALLATION. Do not remove ballast until tank slab has been poured. Do not set remote 
<br />pump motor until ballast water hos been removed from tank. 
<br />1.5 DOABLE WALL FRP TANK INSTALLATION: 
<br />A. MATERIALS: 
<br />1. Double-wall fiberglass reinforced plastic (FRP) storage tanks as supplied by Owner are to be 
<br />installed by Contractor in accordance with the plans and specifications as supplied by 
<br />m,anufaclarer. 
<br />2. Other Contractor supplied equipment included vapor recovery (when specified) Phase I 
<br />Assemblies: Adapters, dust caps and nameplate holders. Phase it Equipment; Ari Recirculation 
<br />valve, high hose retractor, nozzle swivels, flow limiter, anti -kink springs, swivel stops, clamps, 
<br />extension, 
<br />1.6 HANDLING OF FRP TANKS; 
<br />f -I the n from the deliver vehicle. 
<br />A. RESPONSIBILITY: The of sufficient 
<br />ter is responsible or off-loading us e to ks y 
<br />A crane or backhoe of su Hicient lilting capacity must be used. The weight of the double wall FRP 
<br />tank is approximately 5000 - 6000 pounds, 
<br />B. LIFTING & MOVING: When lifting or moving on FRP tank, always use properly sized equipment and 
<br />lift by lifting lug(s). On large tanks, greater than 8' diameter, use a spreader bar to ensure a lift angle 
<br />of at least 45' at each lifting lug, Never roll or use cables or chains around an FRP tank. Set on 
<br />smooth ground, free of rocks and foreign objects, 
<br />EXCEPTION - Tank can be rolled up to 90' on a smooth clean surface when performing the "pre- 
<br />installation" pressure lest. 
<br />C. CHOCKING: Tanks are to be chocked In accordance with manufacturer's recommendation until 
<br />ready for installation. If windy conditions exist or are expected, anchor tanks using minimum 1/2" 
<br />nylon or hemp rope over each lank and secure to stakes of adequate size to prevent movement of 
<br />the tanks. 
<br />D. OPENINGS: All tanks are shipped with dust covers or steel plugs in each opening. Dust covers are to 
<br />remain irk each opening until ready for the pre-instaltalion pressure test. All tanks must have either a 
<br />dust captor steel plugs in place or a 5 psi pressure relief valve in place at all times. 
<br />E. DAMAGE: vI 
<br />1. Asped all tanks carefully for signs of damage upon receipt. Note any damage on the shipping 
<br />documents and notify the Owner Rep. Contact the tank manufacturer for additional 
<br />inforrl,atlon. 
<br />2. If the tank is damaged of any other time, do not attempt repairs. Notify Owner Rep, who will 
<br />detemine the course of action. 
<br />F. SETTING: Set tanks on prepared bed with a slope downward toward the fill end of the tank. A slope 
<br />of 3" diflerence between the two extreme openings of the tank is desired. The acceptable range of 
<br />slope is 4" maximum and 2" minimum; with the fill end lower than remote pump and of the lank. 
<br />Tanks that exceed the acceptable slope or that slope downward to the remote pump end are 
<br />improperly set and must be reset. 
<br />G. INSTALLATION WITH APPROVED MATERIALS: 
<br />1. Place a 12" lift of bockfill evenly around the tanks. Push backfill completely underneath the tank 
<br />between the ribs and under theendcops. Procedure can be done from bank or adjacent tank top, 
<br />If a man will be in the hole to "work" the bit i!1, hole must be shared or side sloped as 
<br />prescribed by current OSHA regulations. 
<br />2. Place second 12" lift or backiill evenly around the tanks, Again, repeat the "working" or backfill 
<br />between the ribs and under the end caps. Add backfill evenly around the tanks up to the tops 
<br />Of the tanks. 
<br />3. Backfill to subgrade after piping and testing is completed, 
<br />H. INSTALLATION WITH ALTERNATE MATERIALS: All alternate materials most receive written approval from 
<br />the tank manufacturer and the Owner representative. 
<br />1.7 TANK TESTING 
<br />A. PRE -INSTALLATION TEST SET UP: Prior to the pre -installation test, all shipping pads most be 
<br />removed from the tank and the vacuum on the annular space must be released, 
<br />A vacuum on the annular space is not substitute for the pre -installation test. All installation tests 
<br />must be performed and recorded on company supplied forms. 
<br />B. NOTIFICATION: 
<br />The Owner Rep., MUST observe all tests, Notify of least 24 hours in advance of any tests. 
<br />C. PRESSURE APPLICATION SYSTEM: 
<br />The pressure application system is to have two pressure gauges (range 0 to 10 psi with 5 psi 
<br />pressure reliefs) in the system, both in good condition and having been tested and calibrated within 
<br />a three-month period prior to the tank lest (copy of the lest and calibration data to be furnished to 
<br />the Owner Rep. upon request). 
<br />USE EXTREME CARE AROUND AND NEAR THE PRESSURIZED TANK. Relieve the pressure prior to 
<br />moving the tank or removingon fittings. 
<br />Never pressurize the secondary router) lock without pressurizing the primary (inner) tank first. 
<br />0. LEAKING TANKS, 
<br />DO NOT install a tank which shows any evidence of a leak. The Owner Rep Is to be notified of any 
<br />damage and will determine the course of action to be followed. 
<br />E. SCOPE OF WORK: 
<br />The Contractor Is responsible for all labor, material and equipment necessary to conduct the 
<br />following Ni 
<br />Pre -Installation Pressure Test, Air 
<br />After-Instdlallor Pressure Test, Air or Hydrostatic 
<br />GENERAL NOTES 
<br />1. SET TANK DEPTH TO ALLOW PRODUCT, VAPOR, AND VENT LINES 
<br />TO SLOPE 1/4' PER FOOT MIN. DOWN TO TANK. 
<br />2. CONTRACTOR SHALL VERIFY THAT THE TURBINE HEAD WILL. BE 4" TO 6" 
<br />A80VE THE TANK BOTTOM. DO NOT INSTALL TURBINE PUMP ASSEMBLY 
<br />IF IT IS LESS THAN 4" FROM BOTTOM OF TANK. 
<br />3, REMOVE SHIPPING PADS FROM TANKS PRIOR TO INSTALLATION. 
<br />F. ACCEPTABLE "SOAPS": "Seeping" the tank and fittings during the lest is to be done using a small 
<br />garden -type hand -pressurized spray unit, The test soap shall be a high foaming "scop" that bubbles 
<br />easily if In contact with on air leak in the lank but won't bubble due to dispensing from the pressure 
<br />applicator. Acceptable soaps are: 
<br />$earn Test Concentrate" 
<br />"Amway Lac High Soap" 
<br />"47006 Soulhbend Leak Detector" 
<br />or approved equal 
<br />G. PRE -INSTALLATION PRESSURE TEST, AIR: Extreme care is to be used around and near the 
<br />pressurized lank. Never pressurize the secondary (outer) tank without pressurizing the primary 
<br />(inner) tank. 
<br />1. Primary (Inner) Tank Test: 
<br />Tighten all lank fillings. Locale a pressure gauge in the vent/rnorutor filling In the secondary 
<br />(outer) lank. Locale a second pressure gage at a fitting in the manwey and connect the air 
<br />pressure hose to this some tilting. Pressurize the primary (inner) lank to o minimum 4 psi, 
<br />maximum 5 psi, Monitor the pressure gages a minimum of 1/2 hour. There should be no pressure 
<br />increase in the secondary (outer) tank. Soop all lank fittings. 
<br />2. Secondary (external) Tank Test: 
<br />Maintain the pressure in the primary lank. Free the hose from the service fitting by cutting the 
<br />nyon lie. Insert the hose Into the Quick Disconnect check valve (found of the lop of the service 
<br />fitting), This wnI allow air to transfer from the primary to secondary tank. Pressurize. to 5 PSIG. 
<br />Add or remove or via the supply valve as needed and allow the pressure to stabilize, Close 
<br />the voiva on the test manifold. Disconnect the air supply line. Monitor the pressure for one hour. 
<br />Soup the entire exterior of the tank and watch for active air bubbles which indicate a leak. 
<br />valve. the air supply like already Should have been disconnected, Kien the air flow from the supply 
<br />valve sloPs, remove the test manifold, 
<br />Whe 
<br />the test is complete, carefully release the air pressure from the tank by opening the supply 
<br />H. POST-ININSTALLATION PRESSURE TEST, AIR: 
<br />1. Primary (Inner) Tank Test: Perform this test with all tank risers and fittings attached. Tighten all 
<br />tank fittings. Locate a pressure gauge in one of the annular space monitor fittings in the 
<br />secondary (outer) tank, Locate o second pressure gauge with a 5 psi pressure relief, to one of 
<br />the primary inner) lank fittings and connect the air pressure hose to this some filling. Pressurize 
<br />t hie pr imory inner) tank to a minimum of 4 psi (maximum 5 psi). Soap all lank fittings and 
<br />monitor the pressure gauge for a minimum of 1/2 hour. There should be no pressure increase In 
<br />the secondary (outer) fork. 
<br />2. Secondary (outer) tank Test: Disconnect the air supply but maintain the pressure on the primary 
<br />Lack. Pressurize the secondary (outer) tank using o flexible air hose manifold. Connect a pressure 
<br />hose from the primary lank to the annular space monitor fitting, 
<br />Pressurize the secondary tank by opening the manifold valve between the 
<br />primary and secondary tank. If necessary, bring pressure of both tanks to a minimum of 4 psi 
<br />(maximum 5 psi) by reconnecting the air supply to the primary tank. 
<br />Monitor the pressure for 1/2 hour and soap all lank fittings, risers and pipe connections. Upon 
<br />completion of the test, release the air pressure from the secondary tank prior to releasing 
<br />pressure from the rimae tank. Damage to the rimae tank may result Ii h pressure if n 
<br />p e y a y primary y the p ossa a of 
<br />relieved from the secondary tank first. 
<br />Caution: Relieve all took pressure pr(or to removing any fittings. 
<br />I, POST -INSTALLATION PRESSURE TEST, HYDROSTATIC: No lank trial shows any evidence of a leak 
<br />is to be kept in the system. Any damage incurred to the tank during the installation will be ccnlraclars 
<br />responsibility. The Owner Rep. Is to be notified of any damage and will determine the course of 
<br />action to be followed. 
<br />If a hydrostatic test is required by a local agency, the contractor is to isolate the lank for testing and 
<br />reconnect when testing is complete. They hydrostatic test will be obtained by Owner, 
<br />J INTERNAL MEASUREMENTS: Take internal diameter measurements at the fill and the remote e pump 
<br />openings, on both single 
<br />and double wall FRP tanks. The Contractor, witnessed by the Owner 
<br />Rep., is responsible for making and recording on a form provided by the Company, the required 
<br />measurements. Take the first set of measurements prior to placing any backfill around the lank The 
<br />second set of measurements is to be taken when the backfill has reached subgrade (prior to pouring 
<br />to concrete slob). - 
<br />If the difference between two sets of readings is greater than 1 1/2" stop the job, The: Owner Rep. 
<br />is to be notified and will determine the course of action, Contact the tank manufacturer for further 
<br />guido,nce. 
<br />K. BALLASTING: Only the primary (inner) lank shot be used when ballasting the tank. Never fill the 
<br />secondary (outer) tank with a fluid. If the tanks are ballasted, conduct Hydrostatic Test (instead of 
<br />the post -installation air test) an the tank and fittings. 
<br />L. BURIAL DEPTH: The burial depth from the top of the tock to ground level shall be a mhimum of 3 
<br />feet -and a maximum of 7 feet, the fittings, if a manway is used, will be approximately 5 to 6 inches 
<br />off the top of the took. This shall be considered for the slope of the piping and thus may affect the 
<br />Lank burial depth, 
<br />M. VENTING: Vent the annular space between the primary and secondary tank only if required by local 
<br />Jurisdictions- Venting of the annular space is not required by the tank manufacturer. If required, 2 
<br />inch FRP pipe sholl be manifold between the tanks and connected to one vent riser. Do not use the 
<br />primary (product) tank vent to eal the annular space. 
<br />N. INTERSTITIAL MONITOR: A pull string may be in 
<br />the took. Install a new pull string it the string is 
<br />missing, lost or broken. The pull string is not a tank manufacturer worfanly item, Install the 
<br />interstitial monitor at the bottomcenterline of the FRP tank. Insert fish tape through the annular 
<br />space. Tag both the pull string to the probe signal cable at 12.5 ft. plus the burial depth. Attach the 
<br />pull string to the probe and to the fish, Tripe and pull probe into lank. When the tags on the signal 
<br />cable and the pull string match the probe is at the bottom centerline of the took. The pull string is 
<br />to remain in place for future accessibility. 
<br />0. INSTALLING THE CONTAINMENT SUMP: The containment sump must be watertight to prevent 
<br />liquid ingress or egress. Fiberglas inside and outside of tank collar 
<br />P. INSTALLING THE SPILL CONTAINMENT FILLBOX: The spill containment Albox must be liquid light. 
<br />Test all fillboxes by filling with tater for a minimum of one hour, There should be no drop in the 
<br />water level during this test. Do rot drain woter'into the tank. 
<br />1.8 APPROVED MATERIALS 
<br />A. APPROVED BACKFILL MATERIALS:. 
<br />L PEA GRAVEL: A dean, naturally rounded aggregate with a 1/8" minimum and a 3/4" maximum 
<br />diiorneter. Up to 57 of the particles may pass through a 48 sieve; 
<br />2, STONE OR GRAVEL CRUSHING$: Washed material with a particle size between 1/8" and 1/2". Up 
<br />to 5% of the particles may pass through a 48 sieve. 
<br />NOTE: Approved materials mustbe dry, free of Ice and snow, and meet ASTM C-33, Paragraph 7.1 
<br />for quality and soundness. The dry gavel density must be a minimum of 95 pounds per cubic foot. 
<br />B. TANK HOLE LINER: Contractor is to provided a Filter Fabric Tank Hole Liner when: 
<br />1. Tank hole is unstable soil, or 
<br />2. Specified by Owner Rep. The entire lank hold (sides and bottom) shall be covered. Lay the 
<br />fabric with 2 foot minimum overlops. 
<br />NOTE: Bedding material, tie -dawn "logs" and sample wells are to be placed on the top of the filter fabric. 
<br />Excess fabric at top of the hole should be folded over the backfill material at subgrade level. 
<br />C, APPROVED FILTER FABRIC MATERIAL: 
<br />Reemay Inc - Typor 3401 or Typor 3341 
<br />Phillips Fibers Corp. - 'Supac 4Np" fabric 
<br />Hoechst Coldness Corp. - Trsviro $1120 
<br />or fabric approved by the tank manufacturer. 
<br />to 
<br />a'I 
<br />I 
<br />�,m 
<br />SII 
<br />4I 
<br />Y O 
<br />L 
<br />1 
<br />.S:N 
<br />--'- 
<br />I 
<br />�/- 
<br />' I - 
<br />I ---4" ALUMrUM FILL TUBE W/POSITIVE SHUT OFF 
<br />I �r 
<br />MONITGRIPROBE TO LOW 
<br />I END OF ANK. 
<br />11 
<br />II 
<br />III 
<br />1 
<br />I I 
<br />SLOPE TANK 1" IN 10' 
<br />I DOWN TOAA DS FILL ENO 
<br />�. Id 1 1 
<br />STEEL PLATES UNDER EACH 
<br />OPENING BY TANK MANUFACTURER-' 
<br />MIN. 
<br />VERIFY W/ TANK MFG, 
<br />20,000 GAL. FIBERGLASS TANK SECTION 
<br />SCALE: 1/4" . V-0" 
<br />U) EV XULU, la 
<br />TUBE 
<br />OF FIBERGLASS OVERLAY 
<br />STEEL PLATE 
<br />7 
<br />--PEA GRAVEL 
<br />BACKFILL 
<br />2,p 
<br />\ 41. 
<br />fi YI� 
<br />SEE SET. B BELOW 
<br />I I 
<br />I I 
<br />I I 
<br />I I 
<br />I I 
<br />PEA GRAVEL 
<br />BACKFILL 
<br />LJ 
<br />1 1 k 
<br />- 
<br />MIN. 
<br />- --PUMP 
<br />TUBE 
<br />4" 
<br />`-- STEEL PLATE 
<br />DE`t &5L B 
<br />MIN. 
<br />SPECIFICATIONS 
<br />1.3 EXCAVATION AND BACKFILL: 
<br />A. EXCAVATION; If unexpected water condition or rock is encountered, immediately contact the 
<br />Owner Rep. for instructions before proceeding with the excavation. 
<br />B. TANK HOLE SIZE IN STABLE SOIL: Size excavation perimeter to allow 36" minimum between tanks 
<br />antl 24" minimum between tank sides and end caps and the wall of the tank hole, 
<br />C. TANK HOLE SIZE IN UNSTABLE SOIL: 
<br />1. Unstable soil is defined as having less than 750 lbs./sq. 1l. cohesion, as calculated from on 
<br />unconfined compression test, or soils with an ultimate bearing capacity of less then 3,500 
<br />lbs./sq.ft Loose sand, muck, bog, peat, swamp or landfill where soil is soft are generally 
<br />considered unstable sails. 
<br />2. Size excavation perimeter to allow 36" minimum between tanks and a minimum of half the tank 
<br />diameter between the lank sides/end caps and the wall of the lank hole. 
<br />rubric lie hole f FRP tanks in soil, 
<br />J. Filter abrl- will be used to n tank oil or R ll s unstable 
<br />4. Permanent o shoring may be used la stabilize the walls of the Conk hole, le the discretion of the 
<br />Contractor and/or Owner Rep. If permanent shoring is used, fallow "Stable Sail" size criteria. 
<br />Refer to "Alternate Backfill Materials", below. 
<br />D. DEPTH OF TANK HOLE. 
<br />1. Contractor is responsible for establishing the tank hole depth, considering the length of piping 
<br />runs, to the pump blocks and vent risers, pipe burial depth, yard slope and the following criteria; 
<br />(Measure at the Remove Pump opening), 
<br />o. FRP: The minimum depth of cover is 4'-0" and the maximum is 7'-0". 
<br />E, SAFETY REOUIRE.MENT: 
<br />No person shall enter a tank hole excavation below the 5 ft. deep level unless the walls are shored 
<br />or side sloped as prescribed by current OSHA regulations. No exceptions. State or local requirements 
<br />that are more restrictive than Company specifications are to be adhered to as though specified in 
<br />Company specifications. The Contractor is responsible for any design, materials, equipment, permits, 
<br />etc., for shoring or side sloping a hole. 
<br />F. FILL AND BACKFILL: 
<br />All fill material shall be of granular nature, free train vegetation and extraneous material. Owner 
<br />Repshall inspect and approve the material before it is spread Spread material in lifts not to exceed 
<br />12 inches and tamp thoroughly, when required by local code, Contractor shall provide a compaction 
<br />lest far certification of fill. 
<br />1.4 BALLAST 
<br />A. MATERIALS 
<br />Water is to be used as a ballast under all conditions where ballost is required. 
<br />B. DRY HOLE CONDITION: 
<br />Tonks, with backfill to lop of tanks, must be ballasted if there is any chance that surface or 
<br />subsurface water will enter the lank hole to a depth of 23" or greater above the bottom of the 
<br />tanks. 
<br />C. WET HOLE CONDITION; 
<br />Aie mpt to pumpwater from the tank hole to maintain a "Dr Hole Condition". If unable to obtain 
<br />o 'Pry Hole Condition",Owner Rep. n "l be and be and will p!ermine the course of action h ebe 
<br />, 
<br />followed, Install filter fabric, lie -down "logs" and bedding as specified elsewhere. Set tank in hale, 
<br />partially fill with water until it sinks firmly on the bed. Use only enough water to behest tank until 
<br />backfill is to top of tonk. After backfill to top of tank, fill tank with water until completion of 
<br />instolletion. 
<br />CAUTION - BALLAST LEVEL MUST NEVER EXCEED WATER OR BACKFILL LEVEL IN THE HOLE 
<br />DURING INSTALLATION. Do not remove ballast until tank slab has been poured. Do not set remote 
<br />pump motor until ballast water hos been removed from tank. 
<br />1.5 DOABLE WALL FRP TANK INSTALLATION: 
<br />A. MATERIALS: 
<br />1. Double-wall fiberglass reinforced plastic (FRP) storage tanks as supplied by Owner are to be 
<br />installed by Contractor in accordance with the plans and specifications as supplied by 
<br />m,anufaclarer. 
<br />2. Other Contractor supplied equipment included vapor recovery (when specified) Phase I 
<br />Assemblies: Adapters, dust caps and nameplate holders. Phase it Equipment; Ari Recirculation 
<br />valve, high hose retractor, nozzle swivels, flow limiter, anti -kink springs, swivel stops, clamps, 
<br />extension, 
<br />1.6 HANDLING OF FRP TANKS; 
<br />f -I the n from the deliver vehicle. 
<br />A. RESPONSIBILITY: The of sufficient 
<br />ter is responsible or off-loading us e to ks y 
<br />A crane or backhoe of su Hicient lilting capacity must be used. The weight of the double wall FRP 
<br />tank is approximately 5000 - 6000 pounds, 
<br />B. LIFTING & MOVING: When lifting or moving on FRP tank, always use properly sized equipment and 
<br />lift by lifting lug(s). On large tanks, greater than 8' diameter, use a spreader bar to ensure a lift angle 
<br />of at least 45' at each lifting lug, Never roll or use cables or chains around an FRP tank. Set on 
<br />smooth ground, free of rocks and foreign objects, 
<br />EXCEPTION - Tank can be rolled up to 90' on a smooth clean surface when performing the "pre- 
<br />installation" pressure lest. 
<br />C. CHOCKING: Tanks are to be chocked In accordance with manufacturer's recommendation until 
<br />ready for installation. If windy conditions exist or are expected, anchor tanks using minimum 1/2" 
<br />nylon or hemp rope over each lank and secure to stakes of adequate size to prevent movement of 
<br />the tanks. 
<br />D. OPENINGS: All tanks are shipped with dust covers or steel plugs in each opening. Dust covers are to 
<br />remain irk each opening until ready for the pre-instaltalion pressure test. All tanks must have either a 
<br />dust captor steel plugs in place or a 5 psi pressure relief valve in place at all times. 
<br />E. DAMAGE: vI 
<br />1. Asped all tanks carefully for signs of damage upon receipt. Note any damage on the shipping 
<br />documents and notify the Owner Rep. Contact the tank manufacturer for additional 
<br />inforrl,atlon. 
<br />2. If the tank is damaged of any other time, do not attempt repairs. Notify Owner Rep, who will 
<br />detemine the course of action. 
<br />F. SETTING: Set tanks on prepared bed with a slope downward toward the fill end of the tank. A slope 
<br />of 3" diflerence between the two extreme openings of the tank is desired. The acceptable range of 
<br />slope is 4" maximum and 2" minimum; with the fill end lower than remote pump and of the lank. 
<br />Tanks that exceed the acceptable slope or that slope downward to the remote pump end are 
<br />improperly set and must be reset. 
<br />G. INSTALLATION WITH APPROVED MATERIALS: 
<br />1. Place a 12" lift of bockfill evenly around the tanks. Push backfill completely underneath the tank 
<br />between the ribs and under theendcops. Procedure can be done from bank or adjacent tank top, 
<br />If a man will be in the hole to "work" the bit i!1, hole must be shared or side sloped as 
<br />prescribed by current OSHA regulations. 
<br />2. Place second 12" lift or backiill evenly around the tanks, Again, repeat the "working" or backfill 
<br />between the ribs and under the end caps. Add backfill evenly around the tanks up to the tops 
<br />Of the tanks. 
<br />3. Backfill to subgrade after piping and testing is completed, 
<br />H. INSTALLATION WITH ALTERNATE MATERIALS: All alternate materials most receive written approval from 
<br />the tank manufacturer and the Owner representative. 
<br />1.7 TANK TESTING 
<br />A. PRE -INSTALLATION TEST SET UP: Prior to the pre -installation test, all shipping pads most be 
<br />removed from the tank and the vacuum on the annular space must be released, 
<br />A vacuum on the annular space is not substitute for the pre -installation test. All installation tests 
<br />must be performed and recorded on company supplied forms. 
<br />B. NOTIFICATION: 
<br />The Owner Rep., MUST observe all tests, Notify of least 24 hours in advance of any tests. 
<br />C. PRESSURE APPLICATION SYSTEM: 
<br />The pressure application system is to have two pressure gauges (range 0 to 10 psi with 5 psi 
<br />pressure reliefs) in the system, both in good condition and having been tested and calibrated within 
<br />a three-month period prior to the tank lest (copy of the lest and calibration data to be furnished to 
<br />the Owner Rep. upon request). 
<br />USE EXTREME CARE AROUND AND NEAR THE PRESSURIZED TANK. Relieve the pressure prior to 
<br />moving the tank or removingon fittings. 
<br />Never pressurize the secondary router) lock without pressurizing the primary (inner) tank first. 
<br />0. LEAKING TANKS, 
<br />DO NOT install a tank which shows any evidence of a leak. The Owner Rep Is to be notified of any 
<br />damage and will determine the course of action to be followed. 
<br />E. SCOPE OF WORK: 
<br />The Contractor Is responsible for all labor, material and equipment necessary to conduct the 
<br />following Ni 
<br />Pre -Installation Pressure Test, Air 
<br />After-Instdlallor Pressure Test, Air or Hydrostatic 
<br />GENERAL NOTES 
<br />1. SET TANK DEPTH TO ALLOW PRODUCT, VAPOR, AND VENT LINES 
<br />TO SLOPE 1/4' PER FOOT MIN. DOWN TO TANK. 
<br />2. CONTRACTOR SHALL VERIFY THAT THE TURBINE HEAD WILL. BE 4" TO 6" 
<br />A80VE THE TANK BOTTOM. DO NOT INSTALL TURBINE PUMP ASSEMBLY 
<br />IF IT IS LESS THAN 4" FROM BOTTOM OF TANK. 
<br />3, REMOVE SHIPPING PADS FROM TANKS PRIOR TO INSTALLATION. 
<br />F. ACCEPTABLE "SOAPS": "Seeping" the tank and fittings during the lest is to be done using a small 
<br />garden -type hand -pressurized spray unit, The test soap shall be a high foaming "scop" that bubbles 
<br />easily if In contact with on air leak in the lank but won't bubble due to dispensing from the pressure 
<br />applicator. Acceptable soaps are: 
<br />$earn Test Concentrate" 
<br />"Amway Lac High Soap" 
<br />"47006 Soulhbend Leak Detector" 
<br />or approved equal 
<br />G. PRE -INSTALLATION PRESSURE TEST, AIR: Extreme care is to be used around and near the 
<br />pressurized lank. Never pressurize the secondary (outer) tank without pressurizing the primary 
<br />(inner) tank. 
<br />1. Primary (Inner) Tank Test: 
<br />Tighten all lank fillings. Locale a pressure gauge in the vent/rnorutor filling In the secondary 
<br />(outer) lank. Locale a second pressure gage at a fitting in the manwey and connect the air 
<br />pressure hose to this some tilting. Pressurize the primary (inner) lank to o minimum 4 psi, 
<br />maximum 5 psi, Monitor the pressure gages a minimum of 1/2 hour. There should be no pressure 
<br />increase in the secondary (outer) tank. Soop all lank fittings. 
<br />2. Secondary (external) Tank Test: 
<br />Maintain the pressure in the primary lank. Free the hose from the service fitting by cutting the 
<br />nyon lie. Insert the hose Into the Quick Disconnect check valve (found of the lop of the service 
<br />fitting), This wnI allow air to transfer from the primary to secondary tank. Pressurize. to 5 PSIG. 
<br />Add or remove or via the supply valve as needed and allow the pressure to stabilize, Close 
<br />the voiva on the test manifold. Disconnect the air supply line. Monitor the pressure for one hour. 
<br />Soup the entire exterior of the tank and watch for active air bubbles which indicate a leak. 
<br />valve. the air supply like already Should have been disconnected, Kien the air flow from the supply 
<br />valve sloPs, remove the test manifold, 
<br />Whe 
<br />the test is complete, carefully release the air pressure from the tank by opening the supply 
<br />H. POST-ININSTALLATION PRESSURE TEST, AIR: 
<br />1. Primary (Inner) Tank Test: Perform this test with all tank risers and fittings attached. Tighten all 
<br />tank fittings. Locate a pressure gauge in one of the annular space monitor fittings in the 
<br />secondary (outer) tank, Locate o second pressure gauge with a 5 psi pressure relief, to one of 
<br />the primary inner) lank fittings and connect the air pressure hose to this some filling. Pressurize 
<br />t hie pr imory inner) tank to a minimum of 4 psi (maximum 5 psi). Soap all lank fittings and 
<br />monitor the pressure gauge for a minimum of 1/2 hour. There should be no pressure increase In 
<br />the secondary (outer) fork. 
<br />2. Secondary (outer) tank Test: Disconnect the air supply but maintain the pressure on the primary 
<br />Lack. Pressurize the secondary (outer) tank using o flexible air hose manifold. Connect a pressure 
<br />hose from the primary lank to the annular space monitor fitting, 
<br />Pressurize the secondary tank by opening the manifold valve between the 
<br />primary and secondary tank. If necessary, bring pressure of both tanks to a minimum of 4 psi 
<br />(maximum 5 psi) by reconnecting the air supply to the primary tank. 
<br />Monitor the pressure for 1/2 hour and soap all lank fittings, risers and pipe connections. Upon 
<br />completion of the test, release the air pressure from the secondary tank prior to releasing 
<br />pressure from the rimae tank. Damage to the rimae tank may result Ii h pressure if n 
<br />p e y a y primary y the p ossa a of 
<br />relieved from the secondary tank first. 
<br />Caution: Relieve all took pressure pr(or to removing any fittings. 
<br />I, POST -INSTALLATION PRESSURE TEST, HYDROSTATIC: No lank trial shows any evidence of a leak 
<br />is to be kept in the system. Any damage incurred to the tank during the installation will be ccnlraclars 
<br />responsibility. The Owner Rep. Is to be notified of any damage and will determine the course of 
<br />action to be followed. 
<br />If a hydrostatic test is required by a local agency, the contractor is to isolate the lank for testing and 
<br />reconnect when testing is complete. They hydrostatic test will be obtained by Owner, 
<br />J INTERNAL MEASUREMENTS: Take internal diameter measurements at the fill and the remote e pump 
<br />openings, on both single 
<br />and double wall FRP tanks. The Contractor, witnessed by the Owner 
<br />Rep., is responsible for making and recording on a form provided by the Company, the required 
<br />measurements. Take the first set of measurements prior to placing any backfill around the lank The 
<br />second set of measurements is to be taken when the backfill has reached subgrade (prior to pouring 
<br />to concrete slob). - 
<br />If the difference between two sets of readings is greater than 1 1/2" stop the job, The: Owner Rep. 
<br />is to be notified and will determine the course of action, Contact the tank manufacturer for further 
<br />guido,nce. 
<br />K. BALLASTING: Only the primary (inner) lank shot be used when ballasting the tank. Never fill the 
<br />secondary (outer) tank with a fluid. If the tanks are ballasted, conduct Hydrostatic Test (instead of 
<br />the post -installation air test) an the tank and fittings. 
<br />L. BURIAL DEPTH: The burial depth from the top of the tock to ground level shall be a mhimum of 3 
<br />feet -and a maximum of 7 feet, the fittings, if a manway is used, will be approximately 5 to 6 inches 
<br />off the top of the took. This shall be considered for the slope of the piping and thus may affect the 
<br />Lank burial depth, 
<br />M. VENTING: Vent the annular space between the primary and secondary tank only if required by local 
<br />Jurisdictions- Venting of the annular space is not required by the tank manufacturer. If required, 2 
<br />inch FRP pipe sholl be manifold between the tanks and connected to one vent riser. Do not use the 
<br />primary (product) tank vent to eal the annular space. 
<br />N. INTERSTITIAL MONITOR: A pull string may be in 
<br />the took. Install a new pull string it the string is 
<br />missing, lost or broken. The pull string is not a tank manufacturer worfanly item, Install the 
<br />interstitial monitor at the bottomcenterline of the FRP tank. Insert fish tape through the annular 
<br />space. Tag both the pull string to the probe signal cable at 12.5 ft. plus the burial depth. Attach the 
<br />pull string to the probe and to the fish, Tripe and pull probe into lank. When the tags on the signal 
<br />cable and the pull string match the probe is at the bottom centerline of the took. The pull string is 
<br />to remain in place for future accessibility. 
<br />0. INSTALLING THE CONTAINMENT SUMP: The containment sump must be watertight to prevent 
<br />liquid ingress or egress. Fiberglas inside and outside of tank collar 
<br />P. INSTALLING THE SPILL CONTAINMENT FILLBOX: The spill containment Albox must be liquid light. 
<br />Test all fillboxes by filling with tater for a minimum of one hour, There should be no drop in the 
<br />water level during this test. Do rot drain woter'into the tank. 
<br />1.8 APPROVED MATERIALS 
<br />A. APPROVED BACKFILL MATERIALS:. 
<br />L PEA GRAVEL: A dean, naturally rounded aggregate with a 1/8" minimum and a 3/4" maximum 
<br />diiorneter. Up to 57 of the particles may pass through a 48 sieve; 
<br />2, STONE OR GRAVEL CRUSHING$: Washed material with a particle size between 1/8" and 1/2". Up 
<br />to 5% of the particles may pass through a 48 sieve. 
<br />NOTE: Approved materials mustbe dry, free of Ice and snow, and meet ASTM C-33, Paragraph 7.1 
<br />for quality and soundness. The dry gavel density must be a minimum of 95 pounds per cubic foot. 
<br />B. TANK HOLE LINER: Contractor is to provided a Filter Fabric Tank Hole Liner when: 
<br />1. Tank hole is unstable soil, or 
<br />2. Specified by Owner Rep. The entire lank hold (sides and bottom) shall be covered. Lay the 
<br />fabric with 2 foot minimum overlops. 
<br />NOTE: Bedding material, tie -dawn "logs" and sample wells are to be placed on the top of the filter fabric. 
<br />Excess fabric at top of the hole should be folded over the backfill material at subgrade level. 
<br />C, APPROVED FILTER FABRIC MATERIAL: 
<br />Reemay Inc - Typor 3401 or Typor 3341 
<br />Phillips Fibers Corp. - 'Supac 4Np" fabric 
<br />Hoechst Coldness Corp. - Trsviro $1120 
<br />or fabric approved by the tank manufacturer. 
<br />Ininit 
<br />r th 
<br />Z Z - 
<br />ii ui 6'Oil L d i4'rulgz0i.3- 
<br />In 
<br />® ® 'rl lu 111i uI W u N 
<br />_ _ ,Vu.3u 
<br />L iYI' U 
<br />ll ry e 
<br />ll �,lr,y )L 
<br />�)(1111 O 
<br />H nl'�?F0111 
<br />WZU4- 
<br />;� / t 
<br />cn a 
<br />u ", 2 
<br />S i ill- h � 
<br />Y. U HJ 
<br />Z W sd 
<br />Q a.in 
<br />0 r- ltl C1 
<br />r In IY O 
<br />U1O 
<br />IY 1 14 
<br />1 
<br />PET -3 
<br />OF 8 SHEETS 
<br />Q 
<br />C) 
<br />n 
<br />T 
<br />6T 
<br />6i 
<br />IL 
<br />H 
<br />l 11 
<br />° 
<br />_7 
<br />_I 
<br />C1 
<br />u 
<br />0 
<br />° 
<br />F, 
<br />a 
<br />Ininit 
<br />r th 
<br />Z Z - 
<br />ii ui 6'Oil L d i4'rulgz0i.3- 
<br />In 
<br />® ® 'rl lu 111i uI W u N 
<br />_ _ ,Vu.3u 
<br />L iYI' U 
<br />ll ry e 
<br />ll �,lr,y )L 
<br />�)(1111 O 
<br />H nl'�?F0111 
<br />WZU4- 
<br />;� / t 
<br />cn a 
<br />u ", 2 
<br />S i ill- h � 
<br />Y. U HJ 
<br />Z W sd 
<br />Q a.in 
<br />0 r- ltl C1 
<br />r In IY O 
<br />U1O 
<br />IY 1 14 
<br />1 
<br />PET -3 
<br />OF 8 SHEETS 
<br />
								 |