SWRCB,January 2002 page 2of7 <br /> 4. TANK ANNULAR TESTING <br /> ed By: <br /> Test Method Developr1 Tank Manufacturer X industry Standard :0 professional Engineer <br /> G Other(Spe 1 <br /> Test Method Used: D Pressure X Vacuum <br /> G Hydrostatic <br /> D Other(Specify) <br /> Test Equipment Used:Vacuum Pump and 0-30"Dial Gauge Equipment Resolution: <br /> Tank#Split Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' rUndleaded <br /> X No D Yes D No D Yes D No C Yes ❑No <br /> Tank Capacity: <br /> Tank Material: <br /> Tank Manufacturer. <br /> Product Stored: oline <br /> Wait time between applying <br /> pressurc/vacuum/water and <br /> starting test <br /> Test Start Time: 11:00 am <br /> Initial Reading(R,): -14-14g <br /> Test End Time: 11:30 am <br /> Final Reading(P,r): -14"Hg <br /> Test Duration: 30 minutes <br /> Change in Reading(RrRn): 0 change <br /> Pass/Fail Threshold or Criteria: 0 change=pass <br /> Test Result- X Pass D Fail G Pass 0 Fail D PAN D Fail D Nss D Fail <br /> Was sensor removed For testing? XYes 0N UNA 0Yes C;No DNA. Dyes DNo 0NA DYes DNo <br /> DNA <br /> Was sensor properly replaced and <br /> ifiefunctional after testing? XYes []No DNA DYes DNo DNA DYes DNo DNA Dyes DNo CIA <br /> Comments—(include information on repairs made r'or to testing and recommended allow up farfailed tests) <br /> Tank rook 2 hours to hold 14"Hg <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic amtainment <br /> testing. {Caiifomig Code of Reeularions.Title 23.Section 2637(a)(W <br />