SWRCB,January 2002 <br /> 1i 1► Page 6 of7 <br /> S. F X RISER COINTAWMIENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sumps 0 <br /> Fill Riser Containment Sumps are Present,but were Not Tested ❑ <br /> Test Method Developed By: 0 Sump Mamdhcturer X Industry Standard ❑Professional Engineer <br /> ❑Other(Spec6 <br /> Test Method Used: U Pressure ❑Vacuum X Hydrostatic <br /> ❑Other(Sp¢c ) <br /> Test Equi out Used:Incan TS STS Equipment Resolution: <br /> Fill Sump#81 Fill Sump 091 Fill Sump# Fill Sam # <br /> Sump Diameter: 42" 42" <br /> Sum 48" 48" <br /> Height from Tank Top to Top of IT, 12" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 18" 18" <br /> Electrical Penetration: <br /> Condition of sump prior to Clean Clean <br /> ttsti <br /> Portion of Stum Tested Full Full <br /> StM Material: Fiberglass Fiberglass <br /> Waft time betwecn applying 10 minutes 10 minutes <br /> pressure/vacmmr/water and <br /> starting test: <br /> Test Start Time: 8:55 am 8:55 am <br /> lydtW Reading.OV. 4.6"77 3.2232" <br /> Test End Time: 9:10 ani 9:10 am <br /> Final Readin (R,): 4-6501' 3.2253" <br /> Test Duration: 15 Minutes 15 Minutes <br /> Change in Re {RF-R; : +.0014' +.0021" <br /> Pass/Fail Threshold or Criteria: _.002"=pass <.O02'=VMS <br /> Test ResuNt X Pass Oren X Paas 0 Fail 0 Pass 0 fall 0 Pass ❑Fail <br /> Is there a sensor in the Sump? X Yes d No X Yes ❑No 0 Yes 0 No ❑Yes ONO <br /> Does the sensor alarm when <br /> eithcr product or water is XYes ❑No [INA XYes ❑No ❑NA O Yes ❑No [INA C Yes 0 No [INA <br /> detected? <br /> Was sensor temoved for testing? XYes 0 No DNA XYes 0 No DNA ❑Yea 0 No [INA GYes ❑No 0 NA <br /> Was sensor properly replaced and XYes 0 No ❑NA XYes ❑No ❑NA 0 Yes ❑No ❑NA 0 Yes 0 No [INA <br /> verified functional after testis ? <br /> Comments—(Include information on repairs madd prior to testing,attd rc mended follow-up forfaded tests) <br />