Laserfiche WebLink
Double Wall Fiberglas <br /> Tanks for Fuel Storage <br /> Model DWT-2P and DWT-4 <br /> Specification <br /> Short Form: 7.General Services Administration,Public Building Service Guide <br /> The contractor shall provide double-wall Fiberglas underground storage Specification,PBS:1568. <br /> tanks U.L.labeled for petroleum products in sizes and with fittings as 1.03 Submittals: <br /> shown on the drawings.The tanks shall be manufactured by Owens- a.Shop Drawings:Contractors shall submit copiesof shop drawings <br /> Corning Fiberglas. for each tank.Drawings shall include all critical dimensions and <br /> Tanks shall be tested and installed with pea gravel or approved alternate show locations of all fittings and accessories,i.e.,manways, <br /> backfill material according to the current installation instructions(Owens. ladders,hold-down straps,heating coils,etc.Materials of <br /> Corning Fiberglas publication 3-PE-6304 and 3-PE-12681)provided with construction shall be in accordance with Section 1.02 of this <br /> the tank. specification. <br /> b.Catalog Data:Contractor shall submit copies of manufacturer's <br /> Long Form: Section 13410 literature. <br /> GUIDE SPECIFICATION c.Certification Plate:U.L.labels for petroleum products shall be <br /> OWENS-CORNING FIBERGLAS affixed to each tank. <br /> DOUBLE-WALL REINFORCED d.Installation Instruction$:Contractors shall submit <br /> POLYESTER UNDERGROUND copies of manufacturer's latest installation instructions. <br /> STORAGETANKS e.Calibration Charts:Contractors shall submit copies <br /> of manufacturer's latest calibration charts. <br /> Part I General Part II Products <br /> 1.01 Related Work Specified In Other Sections 2.01 Double-Wall Fiberglas Underground Storage Tanks. <br /> A.Cast-in-Place Concrete:Section 03300 A.Loading Conditions—Tank shall meet the following design criteria: <br /> B.Anchor Bolts:Section 05501 1.External hydrostatic pressure.Buried in ground with 7'of overburden <br /> over the top of the tank,the hole fully flooded and a safety factor of 5:1 <br /> C.Plastic Pipe:Section 15064 against general buckling. <br /> D.Liquid Level Gauges:Section 15174 2.Surface loads:When installed accordingto manufacturer's installation <br /> E.Other Related Work—such as Excavation and Boiler Equipment instructions tanks will withstand surface H-20 axle loads(32,000 <br /> lbs./axle). <br /> 3.Internal load:Primary tank and annular space shall withstand <br /> 1.02 Quality Assurance pressure test of 5 psi on tanks of 4'through 10'diameters.Resulting in <br /> A.Acceptable Manufacturers:Owens-Corning Fiberglas Corp, a 5 to l safety factor. <br /> Toledo,Ohio 4.Tanks shall be designed to support accessory equipment such as <br /> B.Governing Standards: heating coils,ladders,drop tubes,etc.when installed according to <br /> 1.ASTM Specification D4021-81.Glass Fiber Reinforced manufacturer's recommendations and limitations. <br /> Polyester Underground Petroleum Storage Tanks. B.Product Storage Requirements: <br /> 2.U.L.1316.Underwriters Laboratories,Inc.,Glass Fiber 1.All primary tanks must be vented.Tanks are designed for operation <br /> Reinforced Plastic Underground Storage Tanks for Petroleum at atmospheric pressure only,except for use with vapor recovery <br /> Products. systems at a pressure or vacuum of approximately l psi. <br /> 3.National Fire Protection Assoc.(N FPA 30)Flammable and 2.Tanks shall be capable of storing liquids with specific gravity up to 1.1. <br /> Combustible Liquids Code ano(NFPA 31)Standards for Installation of 3.Maximum temperature.Tanks shall be capable of storing gasoline, <br /> Oil Burning Equipment. gasohol(90%gasoline and 10%ethanol mixture),Oxinol-50® <br /> 4.Factory Mutual File J.I.OK6AF.A5 (90.5%gasoline,4.75%methanol,4,75%GTBA),AV gas,jet fuel, <br /> 5.National Sanitation Foundation Testi ng Laboratory,January 1984, diesel fuel or potable water at ambient underground temperatures,or <br /> Standard 15.Plastic Piping System Components And Related Materials, fuel oil at temperatures not to exceed 150 F at the tank interior <br /> Stnsurface. <br /> Sta <br /> 6.Military Specification MIL-T-52777A,dated July 6,1978,Tanks, 4.Tanks shall be chemically inert to petroleum products. <br /> Storage,Underground,Glass Fiber Reinforced Plastic. <br />