STOCKTON GOLF AND COUNTRY CLUB <br /> MAINTENANCE SHOP <br /> Description of Facility Prior to Cleanup: <br /> This facility included a 1000 gallon underground gasoline tank and <br /> a 1000 gallon underground diesel fuel tank. <br /> Cleanup Work Completed: <br /> The tanks were filled with carbon dioxide, uncovered and removed. <br /> Additional soil was removed from under the tanks (approximately 2 <br /> ft. deeper than the tanks) . All soil was retained in a pile <br /> adjacent to the excavation pending results of analyses of soil <br /> samples. Two samples were taken by California Water Labs from the <br /> base of the excavation as shown on Dwg. No. Sk-002 attached. These <br /> analysed as follows: <br /> Sample No. 1 3 3 4 <br /> EDB ND ND <br /> Lead ND ND <br /> Benzene ND ND . 062 ND <br /> Toluene ND ND . 017 ND <br /> Ethyl Benzene ND ND . 039 ND <br /> Xylenes (Total) ND ND .033 ND <br /> Diesel 89 . 0 ND <br /> Gasoline ND ND <br /> Kerosene ND ND <br /> Oil (as motor oil) ND ND <br /> Status OK OK OK OK <br /> * all results are reported in mg/Kg <br /> The contaminated soil pile was sampled by Environeering Inc. <br /> (composite of several locations and depths) . This analysed as <br /> follows: <br /> Sample No. Diesel Other Hydrocarbons Status <br /> 1M & 2M ND ND OK <br /> The contaminated soil removed from the affected area is estimated <br /> to be 12 cubic yards. <br /> Copies of the analytical results from California Water Labs and <br /> Clayton Environmental Consultants are attached. <br />