Laserfiche WebLink
CERTIFICATE OF UNDERGROUND LINE TESTING <br /> NDE ENVIRONMENTAL CORPORATION <br /> 20000 Mariner Avenue, Suite 500 <br /> Torrance, California 90503 <br /> (310) 542-4342 <br /> Test Date: 4 May 1993 Work Order#: 961023 <br /> Client: SHELL OIL COMPANY Site: SHELL #204-7524-0402 <br /> P.O. BOX 4023 1313 E. CHARTER WAY <br /> CONCORD CA 94524 STOCKTON CA 95205 <br /> Attn: KAREN CLARK <br /> The following tests were conducted at the site described above in accordance with all applicable portions of Federal,NEPA,and Local regulations. <br /> PRECISION LINE TEST SUMMARY <br /> Pressure Test Leak <br /> Line Applied Duration Rate Pass/ <br /> No. Product I .D. Type System (psi) (min) (gph) Fail <br /> 1 SU 2000 PRESSURE 50 30 0. 011 PASS <br /> 2 SR 2000 PRESSURE 50 30 0 . 005 PASS <br /> 3 RU 2000 PRESSURE 50 30 0. 008 PASS <br /> 4 <br /> 5 <br /> 6 <br /> LEAK DETECTOR TEST SUMMARY <br /> Line Leak Detector Leak Calibration <br /> No. Product I .D. Present (milliliters) Pass/Fail Serial # <br /> 1 SU 2000 YES 252 PASS 205922152 <br /> 2 SR 2000 YES 252 PASS 407902140 <br /> 3 RU 2000 YES 252 PASS 205922151 <br /> 4 <br /> 5 <br /> 6 <br /> NDE appreciates the opportunity to serve you,and looks forward to working with you in the future.Please call any time,day or night,when you need us. <br /> NDE Customer Service Representative Testing conducted by <br /> F. MILLER M. LEVESQUE <br /> Reviewed by: t7 Technician certification no.: <br /> Be 'aurin Alicea 1405 <br />