Laserfiche WebLink
Test Date: 4 May 1993 Work Order#: 961023 <br /> LINE TEST DATA <br /> Tank 1 Tank 2 Tank 3 Tank 4 Tank 5 Tank 6 <br /> Product: SU 2000 SR 2000 RU 2000 <br /> Pump type: PRESSURE PRESSURE PRESSURE <br /> Pump Make: REDJACKET REDJACKET REDJACKET <br /> Isolator: ELEMENT ELEMENT ELEMENT <br /> Line Material: STEEL STEEL STEEL <br /> Line Length (ft) : 40 40 40 <br /> Line Diameter (in) : 2 2 2 <br /> Test pressure (psi) 50 50 50 <br /> Bleed Back (cc) : 15 20 20 <br /> Test start time: 14 :00 14 :00 14 :35 <br /> Time (1) : 14 :10 14 : 10 14 :45 <br /> Finish PSI : 49 49 48 <br /> Vol Change (cc) : 10 10 15 <br /> Time (2) : 14 :20 14 :20 14 : 55 <br /> Finish PSI : 49 49 48 <br /> Vol Change (cc) : 0 0 0 <br /> Time (3) : 14 :30 14 :30 15 :05 <br /> Finish PSI: 48 49 48 <br /> Vol Change (cc) : 10 0 0 <br /> Volume change-GPH: 0 . 011 0.005 0 . 008 <br /> Pass/Fail: PASS PASS PASS <br /> LINE TEST COMMENTS: <br /> NDE Environmental Corporation-20000 Mariner Avenue Ste 500-Torrance,CA.90503-(310)542-4342 Page l <br />