My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO 2008-2015
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
A
>
AIRPORT
>
1427
>
2300 - Underground Storage Tank Program
>
PR0521942
>
COMPLIANCE INFO 2008-2015
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
12/28/2023 4:15:38 PM
Creation date
11/2/2018 8:03:35 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2008-2015
RECORD_ID
PR0521942
PE
2371
FACILITY_ID
FA0014921
FACILITY_NAME
RANCHO SAN MIGUEL MARKET*
STREET_NUMBER
1427
Direction
S
STREET_NAME
AIRPORT
STREET_TYPE
WAY
City
STOCKTON
Zip
95205
APN
16902016
CURRENT_STATUS
01
SITE_LOCATION
1427 S AIRPORT WAY
P_LOCATION
02
P_DISTRICT
001
QC Status
Approved
Scanner
SJGOV\kblackwell
Supplemental fields
FilePath
\MIGRATIONS\A\AIRPORT\1427\PR0521942\COMPLIANCE INFO 2008-2015.PDF
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
367
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
QCT-25--2013 14:45 Service Station Systems 448 9E38 8888 P-04 <br /> 4. TANK ANNULAR TESTING v� <br /> Test Method Developed By: ©Tank Manufacturer 0Industry Standard Q Professional.Engineer <br /> © Other(Specify) <br /> Test Method Used: p Pressure ®'Vacuum 0 Hydrostatic <br /> 0 Other(Specify) <br /> Test Equipment Used:Test Plugs,venturi pump and gauges Equipment Resolution: 0.5%of span <br /> Tank#87191 <br /> Is Tank Exempt From Testing?' pYes ® No <br /> Tank Capacity: 20k <br /> Tank Material: Steel <br /> Tank Manufacturer; Modern Welding <br /> Product Stored. Gasoline <br /> Wait time between applying <br /> pressure/vacuum/water and 10 milt. <br /> starting test: <br /> Test Start Time: 9:00 am <br /> Initial Reading(Ry): 7"hg <br /> Test End Tirane: 10:00 am <br /> Final Reading(RF): T'hg <br /> Test Diaration: 1 hour <br /> Change in Reading(kr-R): None <br /> Pass/Fail Threshold or Criteria: No detectable loss <br /> Test Result; ® Pass 0 Fail <br /> Was sensor removed for testing? 0 Yes O No[INA <br /> Was sensor properly replaced and <br /> verified functional after testin ? OYes©No Q NA <br /> Comments (include information on repairs made ptior to testing, and recommendedfollow-upfor failed tests) <br /> "Sensor functionality was not confirmed.This procedure is not part of the Secondary Containment testing scope of work". <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. (California Code of Regulations,Title 23,Section 2637(a)(6)) <br />
The URL can be used to link to this page
Your browser does not support the video tag.