Laserfiche WebLink
0 0 R i . <br /> SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING _ <br /> Tcst Method Developed By: X Tank Manufacturer ❑ Industry Standard Q Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: 0 Pressure X Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution: -1/2-30Hg. <br /> Tank# 1&2 Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' ❑Yes x No ❑Yes x No ❑ Yes No ❑Yes ❑No <br /> Tank Capacity: 20K Split 1515 <br /> Tank Material: Jacketed Steel <br /> Tank Manufacturer: K&T Steel <br /> Product Stored: Regular 87/Super 91 <br /> Wait time between applying 30 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 12:05 <br /> Initial Reading(Rj): -10 Hg. <br /> Test End Time: 2:05 <br /> Final Reading(Rr): -10 Hg. <br /> Test Duration: 2 Hours <br /> Change in Reading(RF-R+): 0 Hg. R <br /> Pass/Fail Threshold or Criteria: No loss in Hg. <br /> Test Result: X`Pass ❑FailPass ❑Fail Pass ❑Fail ❑ Pass ❑ Fail <br /> Was sensor removed for testing? X Yes ❑No ❑NA Yes ❑No ❑NA Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> Was sensor properly replaced and X Yes ❑No [INA Yes ❑No [INA Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> verified functional after testin ? <br /> Comments —(include information on repairs made prior to testing, and recommended follow-zip far faided tests) <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23, Section 2637(a)(6)) <br /> Page 2 of Th <br />