My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO 2008-2015
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
A
>
AIRPORT
>
1427
>
2300 - Underground Storage Tank Program
>
PR0521942
>
COMPLIANCE INFO 2008-2015
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
12/28/2023 4:15:38 PM
Creation date
11/2/2018 8:03:35 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2008-2015
RECORD_ID
PR0521942
PE
2371
FACILITY_ID
FA0014921
FACILITY_NAME
RANCHO SAN MIGUEL MARKET*
STREET_NUMBER
1427
Direction
S
STREET_NAME
AIRPORT
STREET_TYPE
WAY
City
STOCKTON
Zip
95205
APN
16902016
CURRENT_STATUS
01
SITE_LOCATION
1427 S AIRPORT WAY
P_LOCATION
02
P_DISTRICT
001
QC Status
Approved
Scanner
SJGOV\kblackwell
Supplemental fields
FilePath
\MIGRATIONS\A\AIRPORT\1427\PR0521942\COMPLIANCE INFO 2008-2015.PDF
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
367
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
. S WRC5, January 2002 Page of <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: ❑ Sump Manufacturer Ll Industry Standard X Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑ UaCUL11]] X Hydrostatic <br /> ❑Other (Sped) <br /> f_Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> LlSump# 1 Sump# 2 Sump # Sump# <br /> Sump Diameter: 42" 42" <br /> Sump Depth: 50" 55" — <br /> Sump Material: Fiberglass Fiberglass <br /> I leight from Tank Top to Top of 16„ 16" <br /> W i*hast Pi in Penetration; <br /> Height fi•otn Tank Top to Lowest 19" 19" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Dry Dry <br /> Portion of Sump Tested' Water Level 22" Water Line 23" <br /> Does turbine shut down when <br /> SUMP sensor detects I iquid(both X Yes ❑No ❑NA X Yes ❑No [INA Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> product and water)?* <br /> Turbine shutdown response time Not Alarmed Not Alarmed <br /> 1 s system programmed for fail-safe X Yes ❑No ❑NA X Yes ❑No ❑NA Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> shutdown? <br /> Was fail-safe verified.to be <br /> a erational?� Yes X No ❑NA Yes X No ❑NA Yes No ❑NA ❑Yes ❑No ❑NA <br /> Wait time between applying water 5 Minutes 5 Minutes <br /> and startingtest: <br /> Test Start Time; 11:55 12:05 <br /> Initial Reading(Rr): .001 .001 <br /> FFinal <br /> nd Time: 12:25 12:35 <br /> Reading(RF): .001 .001 <br /> uration: 30 Minutes 30 Minutes <br /> e in Reading(Rr-Ri): 0 0 <br /> ail Threshold or Criteria: .005/30 Minutes .005/30 Minutes <br /> Result: X Pass ❑Fail X Pass ❑Fail Pass ❑Fail ❑ Pass ❑ Fail <br /> Was sensor removed for testing? X Yes ❑No ❑NA X Yes ❑No ❑NA Yes ❑No 0 NA D Yes ❑No [INA <br /> Was sensor properly replaced and X Yes ❑No ❑NA X Yes ❑No ❑NA Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> verified functional after testin ? <br /> Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> If the entire depth of the sump is not tested, specify how much was tested, If the answer to any of the questions indicated with an <br /> asterisk (*) is"NO"or"NA", the entire sump must be tested, (See SWRC13 LG-160) <br /> Page S of 1 <br />
The URL can be used to link to this page
Your browser does not support the video tag.