Laserfiche WebLink
-SWRCB,January 2002 ! • Page of <br /> S. FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sumps <br /> Fill Riser Containment Sumps are Present, but were Not Tested <br /> Test Method Developed By: ❑Sump Manufacturer 0 Industry Standard X Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: 0 Pressure D Vacuum X Hydrostatic <br /> ❑Other(Specify) _-- <br /> Test Equipment Used: Caldwell L.cvel Change Indicator h;quiprnent Resolution: .0fl2 <br /> Fill Sump#1 Fill Sump #2 Fill Sump # Fill Sump # <br /> Sum Diameter: 42" 42" <br /> Sum Depth: 53" 55" -- <br /> Height from Tank Top to Top of 16" 14" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 26" 25" <br /> Electrical Penetration: <br /> Condition of sump prior to Dry Dry <br /> testing: <br /> Portion of Sump Tested Water Eine 28" Water Line 27" <br /> Sump Material Fiberglass Fiberglass <br /> Wait time between applying 5 Minutes 5 Minutes <br /> water and starting test: - <br /> Test Start Time: 1:35 1:40 _ <br /> Initial Reading(R,): .001 .001 <br /> Test End Time: 2:05 2,10 <br /> Final Reading(RF): ,001 .001 <br /> Test Duration: 30 minutes 30 Minutes <br /> Change in Reading(RF-R,): 0 0 - <br /> Pass/Fail Threshold or Criteria: 005/30 Minutes .005/30 Minutes <br /> Test Result: X Pass', 0 Fail. X Pass D Fail Pass 0 Fail 0 Pass 0 Fail <br /> Is there a sensor in the sump? X Yes D No X Yes D No Yes ❑No 0 Yes ❑No <br /> Does the sensor alarm when <br /> either product or water is X Yes ❑No 0 NA X Yes D No ❑NA Yes 0 No D NA ❑Yes 0 No ❑NA <br /> detected? <br /> Was sensor removed for testing? X Yes D No NA X Yes D No [INA Yes D No 0 NA ❑Yes ❑No LINA <br /> Was sensor properly replaced and X Yes 0 No D NA X Yes 0 No ❑NA Yes ❑No DNA ❑Yes 0 No DNA <br /> verified functional after testing? <br /> Comments— (include information on repairs made prior to testing, and recommendedfollow-tip for failed tests) <br /> Page f of B <br />