Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manufacturer ^industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure X Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution: - %"x-30"Hg. <br /> Tank#1 Tank#2 Tank#3 Tank# <br /> Is Tank Exempt From Testing?' No No No <br /> Tank Capacity: 20K 20K 12K <br /> Tank Material: Glass/Steel Fiberglass Fiberglass <br /> Tank Manufacturer: Trusco Containment Containment <br /> Solutions Solutions <br /> Product Stored: Jet A Jet A Jet A <br /> Wait time between applying 10 Minutes 10 Minutes 10 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 8:40 8:50 9:00 <br /> Initial Reading(Ri): -10"Hg. -10"Hg. -10"Hg. <br /> Test End Time: 10:40 10:50 11:00 <br /> Final Reading(RF): -10"Hg. -10"Hg. -10"Hg. <br /> Test Duration: 2 Hours 2 Hours 2 Hours <br /> Change in Reading(RF-R,): 0"Hg. 0"Hg. 0"Hg. <br /> Pass/Fail Threshold or Criteria: No loss in Hg. ➢ -2"Hg. ➢ -2"Hg. <br /> Test Result: Pass Pass Pass <br /> Was sensor removed for testing? Yes No No <br /> Was sensor properly replaced and Yes N/A N/A <br /> verified functional after testing? <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23, Section 2637(a)(6)) <br />