Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 5. SECONDARY PIPE TESTING <br /> Test Method Developed By: X Piping Manufacturer ❑Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: X Pressure ❑Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Pressure Gauges in Psi/Nitrogen Equipment Resolution: 1/10-15 Psi <br /> Piping Run#1 Piping Run#2 Piping Run#3 Piping Run#4 <br /> Piping Material: Poly Plastic Fiberglass Fiberglass Fiberglass <br /> Piping Manufacturer: Environ Ameron Ameron Ameron <br /> Piping Diameter: 3" 4" 4" 4" <br /> Length of Piping Run: Approx.6' Approx.6' Approx.6' Approx. 10' <br /> Product Stored: Jet A Jet A Jet A Jet A <br /> Method and location of Test boot at STP Test boot at STP Test boot at STP Test boot at Return <br /> piping-run isolation: Piping Sump#1 Piping Sump#2 Piping Sump#3 Pi in Sum #1 <br /> Wait time between applying 5 Minutes 5 Minutes 5 Minutes 5 Minutes <br /> ressure and startin test: <br /> Test Start Time: 8:45 8:55 9:05 9:15 <br /> Initial Reading(Rt): 5 Psi 5 Psi 5 Psi 5 Psi <br /> Test End Time: 9:45 9:55 10:05 10:15 <br /> Final Reading(RF): 5 Psi 5 Psi 5 Psi 5 Psi <br /> Test Duration: 1 Hour 1 Hour 1 Hour 1 Hour <br /> Change in Reading(RF-Rt): 0 Psi 0 Psi 0 Psi 0 Psi <br /> Pass/Fail Threshold or No detectable loss No detectable loss No detectable loss No detectable loss <br /> Criteria: <br /> Test Result: Pass Pass Pass Pass <br /> Comments—(include information on repairs made prior to testing, and recommendedfollow-up forfailed tests) <br />