Laserfiche WebLink
SWRCB,January 2002 Page_of <br /> MAR 2 7 2015 <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manufacturer ❑Industry Standard e - <br /> Other(Spec) <br /> Test Method Used: Pressure X Vacuum Hydrostatic <br /> Other(Spec) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution: -%z"x-30 Hg. <br /> Tank#1 Tank#2 Tank#3 Tank# <br /> Is Tank Exempt From Testing?' No No No <br /> Tank Capacity: 20K 20K 12K <br /> Tank Material: Glass/Steel Fiberglass Fiberglass <br /> Containment Containment <br /> Tank Manufacturer: Trusco <br /> Solutions Solutions <br /> Product Stored: Jet A Jet A Jet A <br /> Wait time between applying 30 Minutes 30 Minutes 30 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 10:00 10:10 10:20 <br /> Initial Reading(R�): -10 Hg. -10 Hg. - 10 Hg. <br /> Test End Time: 12:00 12:10 12:20 <br /> Final Reading(RF): -10 Hg. -10 Hg. -10 Hg. <br /> Test Duration: 2 Hours 2 Hours 2 Hours <br /> Change in Reading(RF-Ri): 0 Hg. 0 Hg. 0 Hg. <br /> Pass/Fail Threshold or Criteria: No loss in Hg. Y -2 Hg. ➢ -2 Hg. <br /> Test Result: Pass Pass Pass <br /> Was sensor removed for testing? Yes No No <br /> Was sensor properly replaced and Yes N/A N/A <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for,/ailed tests) <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />