Laserfiche WebLink
SWRCB,January 2002 Page _of <br /> S .PIPING SUNIP TESTING <br /> Test Method Developed By: ❑Sump Manufacturer a Industry Standard X Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure Vacuum X Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> sump#5 Sump#6 Sump#7 Sump#8 <br /> Sump Diameter: 42" 35"Square 35"Square 35"Square <br /> Sump Depth: 36" 48" 4811 4899 <br /> Sump Material: Fiberglass Fiberglass Fiberglass Fiberglass <br /> Height from Tank Top to Top of 24" 11" 1T' 'f <br /> Highest Piping Penetration: l0 <br /> Height from Tank Top to Lowest <br /> 22" 1 g+, 24" 23" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Dry Dry Dry Dry <br /> Portion of Sump Tested' Water Level 26" Water Level 20" Water Level 26" Water Level 25" <br /> Does turbine shut down when <br /> sump sensor detects liquid(both Yes Yes Yes Yes <br /> product and water)?. <br /> Turbine shutdown response time Not Alarmed Not Alarmed Not Alarmed Not Alarmed <br /> Is system programmed for fail-safe <br /> shutdown?* Yes Yes Yes Yes <br /> Was fail-safe verified to be <br /> o erational?` �No No No No <br /> Wait time between applying waterand startin test: Minutes 5 Minutes 5 Minutes 5 Minutes <br /> Test Start Time: 11:05 11:10 11:55 12:00 <br /> Initial Reading(RI): .001 .001 .001 .001 <br /> Test End Time: 11:35 11:40 12:25 12:30 <br /> Final Reading(RF): .001 .001 .001 ,001 <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading(RF-R,): 0 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005130 Minutes .005130 Minutes .005/30 Minutes .005130 Minutes <br /> Test Result: X Pass ❑Fail X Pass ❑Fail X Pass ❑Fail X Pass ❑Fail <br /> Was sensor removed for testing? X Yes ❑No ❑NA X Yes ❑No [_i NA X Yes No INA X Yes ❑No -INA <br /> Was sensor properly replaced and <br /> verified functional after testin ? X Yes ❑No ❑NA X Yes [7 No I.]NA X Yes ❑No NA X Yes J No ❑NA <br /> Comments—(include information on repairs made prior to testing,and recommendedfollow-u or ailed tests) <br /> ' If the entire depth of the sump is not tested,specify how much was tested. If the answer to Any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />