Laserfiche WebLink
WINTER WARNING <br />-FOR COLD WEATHER ATJO°F DEGREES OR LESS: <br />OBSERVE AND FOLLOW THE WARNINGS BELOW <br />BRAVO SYSTEMS FF -SERIES FLANGE FITTINGS AND F -SERIES <br />FITTINGS ARE THICKER THAN THE TYPICAL FIBERGLASS CLAMSHELLS <br />COMMONLY INSTALLED IN FIBERGLASS PIPING APPLICATIONS. <br />YOU MUST APPLYADEQUATE HEAT TO THE PARTS AND BONDING <br />ADHESIVES TO ALLOW A FULL CURE TIME DURING EXTREME COLD <br />TEMPERATURES. FAILING TO ALLOW THE INSTALLATION TO FULLY <br />CURE MAY CAUSE THE ADHESIVE BOND TO THE FITTING TO FAIL. <br />lAot to"To k =Aw 0 <br />1) PRE -HEAT THE SUMP TO NO MORE THAN 150'F TO ELIMINATE MOISTURE. <br />2) PRE -HEATING COMPONENTS IN EXTREME COLD WEATHER IS CRITICAL: <br />> PRE -HEAT THE FIBERGLASS FITTING THOROUGHLY TO -100°F <br />PRE -HEAT THE ADHESIVE TO -$0°F. DO NOT HEAT CATALYSTH <br />3) DO NOT ASSUME THE ADHESIVE IS CURED BECAUSE IT HAS HARDENED ON THE <br />EXTERIOR. IT MAY ONLY BE A CURED "CRUST" IN THIS TEMPERATURE AND ANY <br />MOVEMENT OR WATER TESTING MAY CAUSE DELAMINATION AND TOTAL FAILURE <br />OF THE BOND. <br />4) DO NOT ADJUST, MOVE, SHIFT OR OTHERWISE DISTURB THE <br />SUMP, FITTINGSâ–º OR PIPING DURING THE CURING PROCESS. <br />5) YOU MUST ENSURE A FULL CURE BEFORE WATER TESTING. FOLLOW <br />Bill YOUR ADHESIVE INSTRUCTIONS FOR TEMPERATURE GUIDELINES. <br />