Laserfiche WebLink
NORTH CAL <br /> CONSTRUCTION Protecting the Environment <br /> P. O. Box 588 Stockton, CA 95201 2091465-5886 General Engineering Class A License No. 505704 <br /> April 7 , 1988 <br /> American Real Estate Group <br /> P . O . Box 830 <br /> French Camp . California 95231 <br /> Attn : Mickey dames <br /> Re : Petro-Tite Tank Test <br /> Dear Mickey : <br /> On April 4 , 1988 , we performed a Petro-Tite Tank Test at Major <br /> Mart : 1235 East Alpine Avenue , Stockton , California . The test <br /> was performed by Randy Aldridge , North Cal Construction <br /> Technician . The NFPA code 329 . 02 criteria for a tight tank <br /> system is a tolerance of . 050 gallons per hour . Because of the <br /> almost infinite variables involved , this is not intended to be a <br /> mathematical tolerance and is not the permission of actual <br /> leakage . <br /> PRECISION TANK TEST <br /> Tank 2 East <br /> Size - 8 , 000 Gallon Tank <br /> Product - Regular <br /> The test showed a postive .016 gallons per <br /> hour . Based on the above criteria , we find <br /> the tank system tested mathematically tight . <br /> This concludes our test and findings on Apri14 , 1988 . If you <br /> have any questions regarding the results , please contact me . For <br /> your convenience North Cal Construction has provided the San <br /> Joaquin Local Health District with the appropriate documents . <br /> Sincerely , <br /> Randy Aldridg <br /> Certified Tank Testing Technician <br /> RA/bm <br /> Encl . <br />