Laserfiche WebLink
NORTH CAL <br /> CONSTRUCTION ProtectingtheEnvironment <br /> P. O. Box 588 Stockton, CA 95201 2091465-5886 General Engineering Class A License No. 505704 <br /> April 7 , 1988 <br /> American Real Estate Group <br /> P . O . Box 830 <br /> French Camp . California 95231 <br /> Attn : Mickey dames <br /> Re : Petro-Tite Tank Test <br /> Dear Mickey : <br /> On April 4 , 1988 , we performed a Petro-Tite Tank Test at <br /> Major Mart: 1235 East Alpine Avenue , Stockton , California . The <br /> test was performed by Randy Aldridge , North Cal Construction <br /> Technician . The NFPA code 329 . 02 criteria for a tight tank <br /> system is a tolerance of . 050 gallons per hour . Because of the <br /> almost infinite variables involved , this is not intended to be a <br /> mathematical tolerance and is not the permission of actual <br /> leakage . <br /> PRECISION TANK TEST <br /> Tank 3 East <br /> Size - 6 ,000 Gallon Tank <br /> Product : Super Unleaded <br /> The test showed a positive .020 gallo•:s per <br /> hour . Based on the above criteria , we find <br /> the tank system tested mathematically tight . <br /> This concludes our test and findings on April 4 , 1988 . If <br /> you have any questions regarding the results , please contact me . <br /> For your convenience North Cal Construction has provided the San <br /> Joaquin Local Health District with the appropriate documents . <br /> Sincerely , gyp <br /> R/enddy Aldridge(/ <br /> op <br /> Certified Tank Testing Technician <br /> RA/bm <br /> Encl . <br />