Laserfiche WebLink
document 'Pressurized Product Deliveries to CSI Underground Tanks" prepared by <br /> Containment Solutions, dated May 12, 2011, that is included in this resubmittal. <br /> 3. Page 7 section G of the Application for Underground Storage Tank Installation Permit <br /> indicates that an approved overfill prevention device must be provided at each tank fill <br /> location. Choose one of the following methods. You may refer to the State Water Resources <br /> Control Board Letter of Guidance 150-2. Submit corrected version. <br /> Response: The Application for Underground Storage Tank Installation Permit has been <br /> revised and is included with this resubmittal. <br /> 4. Page 8 Section I of the Application for Underground Storage Tank Installation Permit lists the <br /> electronic monitoring of the interstitial space as a single Float Veeder-Root 794380-301. <br /> Sheet C3 of the Underground Tank Installation Site Plan, item in circle 9 states a dual float <br /> sensor would be installed. Sheet T2 of the Sump Installation Details, item hexagon 22 <br /> illustrates an image of a dual float sensor. Sheet T5, item hexagon 22 documents single float <br /> sensor Veeder-root 794380-302 would be installed. Item 33 of Fueling System Catalog Cut <br /> Sheets highlighted the single float sensor Veeder-Root 794380301. This location requires a <br /> dual float sensor. Correct the discrepancies. Submit corrected version. <br /> Response: The plans have been revised to reflect the use of a dual float sensor <br /> Veeder-Root 794380-303. <br /> 5. Operating Permit Application Lubrizol Tank Information/ UPCF UST-B should specify <br /> contents as Lubrizol, not fuel additive. <br /> Response: The Operating Permit Application has been revised to reflect Lubrizol. <br /> 6. Tracy Monitoring Plans: <br /> a. Lubrizol: Section X Overfill prevention method indicated "Audible and visual alarm set <br /> at 90% tank capacity" Page 7 section G of the Application for Underground Storage <br /> Tank Installation Permit indicates a mechanical flapper set at 95% tank capacity. Correct <br /> discrepancies. Submit corrected version. <br /> Response: Overfill prevention method has been revised on all portions of the <br /> application to reflect the audible/visual alarm set at 90% tank capacity. <br /> b. Lubrizol: Section V. Pipe Monitoring item 1. Continuous Monitoring should check dry <br /> (sensor VR 794380-323), Liquid filled (sensor VR 794380-304), under vacuum (add <br /> sensor VR 857280-100) <br /> Response: The application has been revised to reflect the required changes and <br /> is included with this resubmittal. <br /> 7. Manteca UPCF forms — No existing UST & Lubrizol Monitoring Plans, Response Plans and <br /> Site Map were submitted with the application. Submit a complete version. <br /> Response: Existing underground storage tank (UST) and new Lubrizol plans and map <br /> have been included in this resubmittal. <br /> 8. The site plan sheet T-5 Items 32-36 are Bravo brand penetration fitting for double wall-walled <br /> sumps but the manufacturer's cut sheets provided was for single-walled sittings. Provide the <br /> cut sheets for the bravo double-wall penetration fittings. <br /> Response: The correct cut sheets have been included with this resubmittal. <br /> 12919c.039.doc <br />