Laserfiche WebLink
Muniappa Naidu [EH] <br />From: Harley Mattson [hmattson@barghausen.com] <br />Sent: Wednesday, January 23, 2008 1:55 PM <br />To: Muniappa Naidu [EH] <br />Cc: Kasey Foley [EH]; File <br />Subject: tank installation note for Costco Gasoline in Manteca (BCE #12919) <br />Hello Mr. Naidu, <br />Page 1 of 1 <br />Will the addition of this note to Sheet T-2 of the Costco Gasoline plans for the proposed fueling <br />facility in Manteca satisfy your agency in order to approve the plans: <br />In unstable excavation, tanks require: Minimum 18 -inches (24 -inches preferred) <br />between adjacent tanks; minimum of Y the tank diameter (5 -foot 3 -inches) from the <br />ends and sides of the tanks to excavation walls. Contact the soils engineer for <br />recommendations. <br />Please find out if this is acceptable and whether or not there are any other outstanding plan <br />check comments that your agency would like us to address prior to approving the UST <br />Installation Permit. If you do have any other plan check comments, we respectfully request <br />that your agency send the comments to us in writing. Thank you. <br />Regards, <br />Harley Mattson I senior Planner I <br />Barghausen Consulting Engineers, Inc. 118215 72nd Avenue South I tient, WA 980321 <br />Phone: (425) 251-6222 1 Facsimile: (425) 251-8782 <br />1/23/2008 <br />