TESTING DOUBLE-WALL TANKS <br />HYDROSTATICALLY MONITORED <br />(WITH LIQUID FILLED ANNULAR SPACE) <br />This tank has a hydrostatic monitoring system that includes <br />a nontoxic colored monitoring fluid (30% calcium chloride) <br />between the tank walls. <br />In the unlikely event of a tank leak, this monitoring fluid will <br />leave a colored trace on the tank. <br />Reservoir Level Check: <br />M <br />♦ Remove the 4" plug from the reservoir fitting. <br />♦ Inspect for monitoring tracer fluid. <br />♦ See Section C1 and C3. <br />♦ if reservoir is completely empty, immediately call Con- <br />tainment Solutions Field Service. <br />Outer Wall Test <br />INSPECTION <br />Step 1 <br />Closely inspect outer wall for any trace of colored moni- <br />toring tracer fluid. <br />NOTE: If a colored fluid is found on the tank surface <br />during any test, discontinue the installation and imme- <br />diately contact Containment Solutions Field Service.. <br />BOTTOM INSPECTION <br />Step 1 <br />Tighten all fitting plugs to the annular space and res- <br />ervoir to avoid spilling monitoring fluid. <br />Step 2 <br />Inspect tank bottom by lifting tank using all lift lugs <br />provided on the tank. <br />Do not stand under tank while tank is in the air. <br />Injury or death could occur. <br />Step 3 <br />After completing inspection of tank bottom, replace tank <br />on shipping pads or on smooth ground. <br />DO NOT <br />♦ Rotate tank. <br />PRESSURIZE TANK <br />Step 1 <br />Connect air compressor line to primary tank fitting. <br />Step 2 <br />A contractor supplied pressure relief valve must be <br />connected to the primary tank for additional protec- <br />tion. The relief valve should be sized and set to prevent <br />the tank from being pressurized in excess of the maxi- <br />mum allowed test pressure. <br />Step 3 <br />Pressurize primary tank to 5 psi maximum. <br />DO NOT <br />♦ Attach air pressure line to any annular space fitting. <br />Do not lift tank with pressure on it. This could result <br />in personal injury. <br />VISUAL AIRISOAP TEST <br />Step 1 <br />Apply a soapy water solution to all fittings and manways. <br />Step 2 <br />Check for leaks as indicated by bubbles. <br />Step 3 <br />If bubbles are present, tighten the plugs or bolts and <br />retest. <br />INNERWALLTEST <br />Step 1 <br />Release pressure from primary tank. <br />Step 2 <br />Remove enough tank fittings to see inside primary tank. <br />Step 3 <br />With a light, look inside for any accumulation of moni- <br />toring tracer fluid. <br />NOTE: If a colored fluid is found on the tank surface <br />during any test, discontinue the installation and im- <br />mediately contact Containment Solutions Field Ser- <br />vice. <br />Step 4 <br />Replace and tighten fitting plug(s). <br />Step 5 <br />Loosen plug to vent annular space. <br />A4. HOLE SIZE <br />NOTE: If tanks are mechanically anchored, additional <br />minimum clearance is required between tanks (see sec- <br />tion A7). <br />STABLE EXCAVATIONS (FIGURE5) <br />CONTINUED ON PAGE 8 <br />