"u- r111r1rnca Ano SUMP CLEARANCES <br />Tanks with Bottom Sumps <br />When installing a tank equipped with a bottom sump, ex- <br />cavating and bedding must be modified to provide: <br />♦ A hole centered at the sump location. <br />♦ Hole should be 12" deep x 24" diameter. <br />After the tank is placed, the void surrounding the sump must be: <br />♦ Hand backfilled and <br />♦ Hand tamped prior to adding backfill around tank or use <br />a long handled curved probe to fill hole. <br />External Piping <br />♦ The pump and attached piping must be free to move with <br />the tank (see figure 23). <br />♦ Use a fill box or street box to isolate the piping from the <br />traffic pad. <br />♦ Take precaution during construction to make sure no <br />damage occurs to the exposed piping and fittings. <br />FIGURE 23 <br />External Piping <br />Isblate'Piping <br />'frorn Traffic - <br />:'slab$ <br />Internal Piping <br />♦ Internal piping must terminate a minimum of: <br />❑ 4" from the tank bottom (4', 6', 8', 10' diameter tanks). <br />❑ 6" from tank bottom (12' diameter tanks). <br />(see figure 24) <br />♦ A fill tube insert must be installed at the tank gauging <br />fitting if the manual dipstick method is used to inventory <br />tanks to ensure the dipstick point of impact is aligned <br />with the tank bottom protector plate. <br />Internal Piping <br />URE 24 <br />C4"min <br />12 <br />"tanks <br />6 mn <br />I <br />A110- FILLING TANKS <br />CAUTION <br />Do not fill tank with product or water for hold-down until <br />backfilling is even with top of tank or tank damage can <br />occur. <br />Exception - "Installation Procedure - Wet Hole" section, <br />A11. VENTING <br />♦ All tanks must be vented. <br />♦ Tanks are designed for operation at atmospheric pres- <br />sure only (except for use with vapor recovery systems <br />provided the pressure or vacuum does not exceed 1 psi.) <br />♦ The vent opening should be the same diameter or larger <br />than the piping used to remove product. <br />♦ For double-wall tanks, if the annular space is vented, it <br />must be vented independently from the primary tank. <br />♦ For hydrostatically monitored double-wall tanks, the an- <br />nular space must be vented at all times. <br />PRESSURIZED PRODUCT DELIVERIES <br />CAUTION <br />Pressurized product deliveries are not recommended <br />AS TANK DAMAGE MAY OCCUR. <br />♦ If the delivery vehicle uses pumps to fill the tank: <br />❑ Install overfill, shut-off equipment in the lines and on <br />the truck to prevent the tank from being overfilled. <br />❑ Overfilling the tank under pressure will damage <br />the tank, even if the tank vent is unrestricted. <br />❑ Do not use a ball Float valve for overfill protection.. <br />Al2. MANWAY AND MANWAY EXTENSIONS <br />M, k, I I <br />Do Not enter tank unless following OSHA guidelines <br />for confined space entry. <br />Entry Can Result In: <br />1 <br />ASPHYXIATION FIRE EXPLOSION <br />G©NTMED ON PAGE 16 <br />15 <br />