Laserfiche WebLink
Monitoring System Certification • • <br /> D. Results of Testing/Servicing <br /> Software Version Installed: 329.00 <br /> Complete the following checklist: <br /> E Yes ❑ No* T Is the audible alarm operational? <br /> E Yes ❑ No* Is the visual alarm operational? <br /> E Yes ❑ No* Were all sensors visually inspected,functionally tested,and confirmed operational? <br /> E Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br /> not interfere with their proper operation? <br /> ❑ Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) <br /> E N/A operational? <br /> E Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br /> ❑ N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate <br /> positive shut-down? (Check all that apply) E Sump/Trench Sensors; E Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failure/disconnection? E Yes; ❑No. <br /> ❑ Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no <br /> E N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank <br /> vt AI'a eRs fill point(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? 90% <br /> ❑ Yes* E No Was any monitoring equipment replaced? If yes,identify specific sensors,probes,or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in Section E,below. <br /> E Yes* ❑ No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br /> ❑Product; E Water. If yes,describe causes in Section E,below. <br /> ❑ Yes E No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> Yes U No* Is all monitorin a ui mento erational er manufacturer's s ecifications� <br /> * In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: <br /> 1- Printer not functioning at present time. Inspector verified Alarm history through computer. <br /> 2-Small amount of water tound in annular space on Diesel I ank. <br /> 3- No set-up was reviewed by Inspector due to printer was not working. <br /> Page 2 of 4 <br /> UN-036-2/4 w .unidomorg <br /> Rev.01 117/08 <br />