Laserfiche WebLink
• ACEIVEL <br /> SWRCB,January 2002 APR 21 2015 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manufacturer ❑Industry Standar.r q sa ineer <br /> ❑Other(Specify) <br /> Test Method Used: a Pressure X Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution: -'/Z"x-30"Hg. <br /> Tank# I 1ank92 Funk#3 Tank# <br /> Is Tank Exempt From Testing?' No No No <br /> Tank Capacity: 12K 12K 12K <br /> Tank Material: Fiberglass Fiberglass Fiberglass <br /> Tank Manufacturer: Owens Corning Owens Coming Owens Coming <br /> Product Stored: Regular 87 Super 91 Diesel <br /> Wait time between applying 30 Minutes 30 Minutes 30 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 10:15 10:15 10:15 <br /> Initial Reading(R,): -10 Hg. -10 Hg. -10 Hg. <br /> Test End Time: 11:15 11:15 11:15 <br /> Final Reading(RP): -10 Hg. -10 Hg. -10 Hg. <br /> Test Duration: 1 Hour 1 Hour 1 Hour <br /> Change in Reading(R,-R,): 0 Hg. 0 Hg. 0 Hg. <br /> Pass/Fail Threshold or Criteria: ➢ -2 Hg. ➢ -2 Hg. ➢ -2 Hg. <br /> Test Result: Pass Pass Pass <br /> Was sensor removed for testing? No No No <br /> Was sensor properly replaced and N/A N/A N/A <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing and recommended follow-up for failed tests) <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23, Section 2637(a)(6)) <br />